2 Parameters
2.2 List of parameters
r3804
CO: Sync-line-drive target frequency / Sync f_target
VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Functions
Not for motor type: -
Min
- [Hz]
Description:
Displays the target frequency for the line-drive synchronization.
Dependency:
Refer to: A07941
r3805
CO: Sync-line-drive frequency difference / Sync f_diff
VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Functions
Not for motor type: -
Min
- [Hz]
Description:
Displays the frequency difference between the measured target frequency and output frequency of the gating unit of
the closed-loop control for line-drive synchronization.
p3806[0...n]
Sync-line-drive frequency difference threshold value / Sync f_diff thresh
VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Functions
Not for motor type: -
Min
0.00 [Hz]
Description:
Sets the threshold value of the frequency difference to activate the closed-loop phase control for line-drive
synchronization.
The closed-loop phase control is activated (r3819.6 = 1), if the frequency difference is less that the threshold value.
r3808
CO: Sync-line-drive phase difference / Sync phase diff
VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Functions
Not for motor type: -
Min
- [°]
Description:
Displays the phase difference between the measured target phase and phase of the gating unit of the closed-loop
control for line-drive synchronization.
p3809[0...n]
Sync-line-drive phase setpoint / Sync phase setp
VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Functions
Not for motor type: -
Min
-180.00 [°]
Description:
Sets the phase setpoint for the line-drive synchronization.
618
Calculated: -
Dyn. index: -
Unit group: -
Scaling: p2000
Max
- [Hz]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: p2000
Max
- [Hz]
Calculated:
CALC_MOD_LIM_REF
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
1.00 [Hz]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: p2005
Max
- [°]
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
179.90 [°]
List Manual (LH2), 07/2016, A5E03263479A
Access level: 2
Func. diagram: 3030, 7020
Unit selection: -
Expert list: 1
Factory setting
- [Hz]
Access level: 2
Func. diagram: 7020
Unit selection: -
Expert list: 1
Factory setting
- [Hz]
Access level: 2
Func. diagram: 7020
Unit selection: -
Expert list: 1
Factory setting
0.10 [Hz]
Access level: 2
Func. diagram: 7020
Unit selection: -
Expert list: 1
Factory setting
- [°]
Access level: 2
Func. diagram: 7020
Unit selection: -
Expert list: 1
Factory setting
0.00 [°]