Siemens G130 List Manual page 644

Hide thumbs Also See for G130:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
p4031
BI: TM31 signal source for terminal DO 1 / TM31 s_src DO 1
TM31
Can be changed: U, T
Data type: Unsigned32 / Binary
P-Group: Commands
Not for motor type: -
Min
-
Description:
Sets the signal source for the digital output DO 1 (X542.4, X542.5, X542.6) of Terminal Module 31 (TM31).
Digital output 1 of TM31 is a relay output.
If the signal at the binector input p4031 is low, then terminal COM 1 (X542.5) is connected to NC 1 (X542.4). This
connection also matches the mechanical quiescent setting of the relay.
If the signal at the binector input p4031 is high, then terminal COM 1 (X542.5) is connected to NO 1 (X542.6).
Note:
DO: Digital Output
NC: Normally Closed contact
NO: Normally Open contact
p4031
BI: TB30 signal source for terminal DO 1 / TB30 s_src DO 1
TB30
Can be changed: U, T
Data type: Unsigned32 / Binary
P-Group: Commands
Not for motor type: -
Min
-
Description:
Sets the signal source for terminal DO 1 (X481.6) of the Terminal Board 30 (TB30).
Note:
DO: Digital Output
p4032
BI: TB30 signal source for terminal DO 2 / TB30 s_src DO 2
TB30
Can be changed: U, T
Data type: Unsigned32 / Binary
P-Group: Commands
Not for motor type: -
Min
-
Description:
Sets the signal source for terminal DO 2 (X481.7) of the Terminal Board 30 (TB30).
Note:
DO: Digital Output
p4033
BI: TB30 signal source for terminal DO 3 / TB30 s_src DO 3
TB30
Can be changed: U, T
Data type: Unsigned32 / Binary
P-Group: Commands
Not for motor type: -
Min
-
Description:
Sets the signal source for terminal DO 3 (X481.8) of the Terminal Board 30 (TB30).
Note:
DO: Digital Output
644
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
List Manual (LH2), 07/2016, A5E03263479A
Access level: 1
Func. diagram: 9549, 9556
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 1
Func. diagram: 9102
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 1
Func. diagram: 9102
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 1
Func. diagram: 9099, 9102
Unit selection: -
Expert list: 1
Factory setting
0
SINAMICS G130/G150

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

SinamicsG150

Table of Contents