Siemens G130 List Manual page 841

Hide thumbs Also See for G130:
Table of Contents

Advertisement

Note:
For value = 99 (automatic) the following applies:
- if a COMM BOARD is not inserted, then the onboard interface (PROFIBUS/PROFINET/USS) communicates via
IF1.
- if a CBE20 is inserted, then the following applies:
-- CU320-2 DP: PROFINET CBE20 communicates via IF1 and PROFIBUS/USS via IF2.
-- CU320-2 PN: PROFINET onboard communicates via IF1 and PROFINET CBE20 via IF2.
- CAN CBC10 always communicates via IF2.
For a value not equal to 99 (automatic) the following applies:
- both indices must be set to a number not equal to 99 (automatic).
A change only becomes effective after POWER ON, reset or download.
p8840
COMM BOARD monitoring time / CB t_monit
CU_G130_PN (COMM
Can be changed: U, T
BOARD, PN CBE20),
Data type: FloatingPoint32
CU_G150_PN (COMM
P-Group: Communications
BOARD, PN CBE20),
Not for motor type: -
CU_G130_DP (COMM
BOARD, PN CBE20),
Min
CU_G150_DP (COMM
0 [ms]
BOARD, PN CBE20)
Description:
Sets the monitoring time to monitor the process data received via COMM BOARD.
If, during this time, the Control Unit does not receive any process data from the COMM BOARD, then an appropriate
message is output.
Dependency:
Refer to: p8835
Note:
This monitoring function only monitors the connection between the Control Unit and COMM BOARD and not the data
traffic on the fieldbus.
For CBE20 firmware version MODBUS TCP (p8835 =5) then the fieldbus data traffic is also monitored.
Value = 0: Monitoring is deactivated.
p8841[0...239]
COMM BOARD send configuration data / CB s config_dat
CU_G130_PN (COMM
Can be changed: U, T
BOARD, PN CBE20),
Data type: Unsigned16
CU_G150_PN (COMM
P-Group: Communications
BOARD, PN CBE20),
Not for motor type: -
CU_G130_DP (COMM
BOARD, PN CBE20),
Min
CU_G150_DP (COMM
0
BOARD, PN CBE20)
Description:
Sets the send configuration data for the COMM BOARD.
The setting is activated with p8842.
Dependency:
Refer to: p8842
Note:
The configuration data are specific to the inserted COMM BOARD.
For CBE20, the configuration data are not relevant.
p8842
Activate COMM BOARD send configuration / CB s config act
CU_G130_PN (COMM
Can be changed: U, T
BOARD, PN CBE20),
Data type: Unsigned16
CU_G150_PN (COMM
P-Group: Communications
BOARD, PN CBE20),
Not for motor type: -
CU_G130_DP (COMM
BOARD, PN CBE20),
Min
CU_G150_DP (COMM
0
BOARD, PN CBE20)
Description:
Activate a modified send configuration for COMM BOARD.
With p8842 = 1, the values in p8841 are transferred to the COMM BOARD and activated. After this, p8842 is
automatically set to zero.
Dependency:
Refer to: p8841
Note:
For CBE20, certain SINAMICS parameters are newly evaluated and activated. An existing, cyclic bus connection is
interrupted.
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
65535000 [ms]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
65535
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
1
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
20 [ms]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 2199, 2200
Unit selection: -
Expert list: 1
Factory setting
0
841