2 Parameters
2.2 List of parameters
p2280
Technology controller proportional gain / Tec_ctrl Kp
VECTOR_G
Can be changed: U, T
(Tech_ctrl)
Data type: FloatingPoint32
P-Group: Technology
Not for motor type: -
Min
0.000
Description:
Sets the proportional gain (P component) of the technology controller.
Dependency:
Refer to: p2252
Note:
p2280 = 0: The proportional gain is disabled.
p2285
Technology controller integral time / Tec_ctrl Tn
VECTOR_G
Can be changed: U, T
(Tech_ctrl)
Data type: FloatingPoint32
P-Group: Technology
Not for motor type: -
Min
0.000 [s]
Description:
Sets the integral time (I component, integrating time constant) of the technology controller.
Dependency:
Refer to: p2252
Note:
p2285 = 0: The integral time is disabled.
p2286[0...n]
BI: Hold technology controller integrator / Tec_ctr integ hold
VECTOR_G
Can be changed: T
(Tech_ctrl)
Data type: Unsigned32 / Binary
P-Group: Technology
Not for motor type: -
Min
-
Description:
Sets the signal source to hold the integrator for the technology controller.
p2289[0...n]
CI: Technology controller pre-control signal / Tec_ctr prectr_sig
VECTOR_G
Can be changed: U, T
(Tech_ctrl)
Data type: Unsigned32 / FloatingPoint32
P-Group: Technology
Not for motor type: -
Min
-
Description:
Sets the signal source for the pre-control signal of the technology controller.
p2291
CO: Technology controller maximum limiting / Tec_ctrl max_lim
VECTOR_G
Can be changed: U, T
(Tech_ctrl)
Data type: FloatingPoint32
P-Group: Technology
Not for motor type: -
Min
-200.00 [%]
Description:
Sets the maximum limit of the technology controller.
Dependency:
Refer to: p2292
Caution:
The maximum limit must always be greater than the minimum limit (p2291 > p2292).
576
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
1000.000
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
60.000 [s]
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: PERCENT
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: PERCENT
Max
200.00 [%]
List Manual (LH2), 07/2016, A5E03263479A
Access level: 2
Func. diagram: 7958
Unit selection: -
Expert list: 1
Factory setting
1.000
Access level: 2
Func. diagram: 7958
Unit selection: -
Expert list: 1
Factory setting
0.000 [s]
Access level: 3
Func. diagram: 7958
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 7958
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 7958
Unit selection: -
Expert list: 1
Factory setting
100.00 [%]