Device type:
r0964[1] = 5200 --> SINAMICS G150 CU320-2 DP
r0964[1] = 5201 --> SINAMICS G150 CU320-2 PN
r0964[1] = 5210 --> SINAMICS G130 CU320-2 DP
r0964[1] = 5211 --> SINAMICS G130 CU320-2 PN
r0965
PROFIdrive profile number / PD profile number
CU_G130_PN,
Can be changed: -
CU_G150_PN,
Data type: Unsigned16
CU_G130_DP,
P-Group: Communications
CU_G150_DP
Not for motor type: -
Min
-
Description:
Displays the PROFIdrive profile number and profile version.
Constant value = 0329 hex.
Byte 1: Profile number = 03 hex = PROFIdrive profile
Byte 2: Profile version = 29 hex = Version 4.1
Note:
When the parameter is read via PROFIdrive, the Octet String 2 data type applies.
p0969
System runtime relative / t_System relative
CU_G130_PN,
Can be changed: T
CU_G150_PN,
Data type: Unsigned32
CU_G130_DP,
P-Group: Displays, signals
CU_G150_DP
Not for motor type: -
Min
0 [ms]
Description:
Displays the system runtime in ms since the last POWER ON.
Note:
The value in p0969 can only be reset to 0.
The value overflows after approx. 49 days.
When the parameter is read via PROFIdrive, the TimeDifference data type applies.
p0970
Reset drive parameters / Drive par reset
CU_G130_PN,
Can be changed: C2(30)
CU_G150_PN,
Data type: Unsigned16
CU_G130_DP,
P-Group: Factory settings
CU_G150_DP
Not for motor type: -
Min
0
Description:
The parameter is used to initiate the reset of the parameters of an individual drive unit.
Parameters p0100, p0205 (only for VECTOR) and the parameters of the basic drive commissioning (p0009) are not
reset (p0107, p0108, p0111, p0112, p0115, p0121, p0130, p0131, p0140, p0141, p0142, p0170, p0186 ... p0189).
These can only be reset using the factory setting of the complete drive unit (p0976).
Value:
0:
1:
5:
6:
10:
11:
12:
30:
100:
Notice:
After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Inactive
Start a parameter reset
Starts a safety parameter reset
Start reset non-safety/safety parameters
Start loading the parameters saved with p0971=10
Start loading the parameters saved with p0971=11
Start loading the parameters saved with p0971=12
Start loading the delivery state saved with p0971=30
Start a BICO interconnection reset
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
4294967295 [ms]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
100
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: 8050, 8060
Unit selection: -
Expert list: 1
Factory setting
0 [ms]
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0