2 Parameters
2.2 List of parameters
p0309[0...n]
Rated motor efficiency / Mot eta_rated
VECTOR_G
Can be changed: C2(1, 3)
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: PMSM, REL
Min
0.0 [%]
Description:
Sets the rated motor efficiency (rating plate).
For a parameter value of 0.0, the power factor is internally calculated and displayed in r0332.
Dependency:
This parameter is only visible for NEMA motors (p0100 = 1, 2).
Refer to: p0100, p0308, r0332
Notice:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note:
The parameter is not used for synchronous motors (p0300 = 2xx).
p0310[0...n]
Rated motor frequency / Mot f_rated
VECTOR_G
Can be changed: C2(1, 3)
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: -
Min
0.000 [Hz]
Description:
Sets the rated motor frequency (rating plate).
Dependency:
The number of pole pairs (r0313) is automatically re-calculated when the parameter is changed (together with
p0311), if p0314 = 0.
The rated frequency is restricted to values between 1.00 Hz and 650.00 Hz.
Refer to: p0311, r0313, p0314
Notice:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
If p0310 is changed during quick commissioning (p0010 = 1), the maximum speed p1082, which is also associated
with quick commissioning, is pre-assigned accordingly. This is not the case when commissioning the motor (p0010 =
3).
p0311[0...n]
Rated motor speed / Mot n_rated
VECTOR_G
Can be changed: C2(1, 3)
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: -
Min
0.00 [rpm]
Description:
Sets the rated motor speed (rating plate).
For VECTOR the following applies (p0107):
For p0311 = 0, the rated motor slip of induction motors is internally calculated and displayed in r0330.
It is especially important to correctly enter the rated motor speed for vector control and slip compensation for U/f
control.
Dependency:
If p0311 is changed and for p0314 = 0, the pole pair (r0313) is re-calculated automatically.
Refer to: p0310, r0313, p0314
Notice:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
If p0311 is changed during quick commissioning (p0010 = 1), the maximum speed p1082, which is also associated
with quick commissioning, is pre-assigned accordingly. This is not the case when commissioning the motor (p0010 =
3).
134
Calculated: -
Dyn. index: MDS, p0130
Unit group: -
Scaling: -
Max
99.9 [%]
Calculated: -
Dyn. index: MDS, p0130
Unit group: -
Scaling: -
Max
3000.000 [Hz]
Calculated: -
Dyn. index: MDS, p0130
Unit group: -
Scaling: -
Max
210000.00 [rpm]
List Manual (LH2), 07/2016, A5E03263479A
Access level: 1
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0.0 [%]
Access level: 1
Func. diagram: 6301
Unit selection: -
Expert list: 1
Factory setting
0.000 [Hz]
Access level: 1
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0.00 [rpm]
SINAMICS G130/G150