2 Parameters
2.2 List of parameters
p0263
Cooling unit fault liquid flow delay time / RKA flow t_del
VECTOR_G
Can be changed: U, T
(Cool_unit), B_INF
Data type: FloatingPoint32
(Cool_unit)
P-Group: Converter
Not for motor type: -
Min
0.0 [s]
Description:
Sets the delay time for the fault "RKA: Liquid flow too low".
The fault is only output if the cause is present for a time longer than is set in this parameter.
Dependency:
Refer to: F49153
p0264
Cooling unit run-on time / RKA run-on time
VECTOR_G
Can be changed: U, T
(Cool_unit), B_INF
Data type: FloatingPoint32
(Cool_unit)
P-Group: Converter
Not for motor type: -
Min
0.0 [s]
Description:
Sets the run-up time of the cooling unit after a switch-off command.
r0265.0...3
BO: Cooling unit control word / RKA STW
VECTOR_G
Can be changed: -
(Cool_unit), B_INF
Data type: Unsigned8
(Cool_unit)
P-Group: Commands
Not for motor type: -
Min
-
Description:
Displays the control word for the cooling unit.
Bit field:
Bit
00
01
02
03
p0266[0...7]
BI: Cooling unit feedback signals signal source / RKA fdbk S_src
VECTOR_G
Can be changed: U, T
(Cool_unit), B_INF
Data type: Unsigned32 / Binary
(Cool_unit)
P-Group: Communications
Not for motor type: -
Min
-
Description:
Sets the signal sources for the feedback signals from the cooling unit.
Index:
[0] = Cooling unit switched on
[1] = Cooling unit ready for switching on
[2] = Cooling unit no alarm present
[3] = Cooling unit no fault present
[4] = Cooling unit no leaked liquid
[5] = Cooling unit liquid flow OK
[6] = Cooling unit conductivity < fault threshold
[7] = Cooling unit conductivity < alarm threshold
124
Signal name
Switch on cooling unit
Message converter off
Acknowledge faults
Leakage sensing OK
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
20.0 [s]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
180.0 [s]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
1 signal
Switch on
OFF
Acknowledgment
No leaked liquid
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: 9795
Unit selection: -
Expert list: 1
Factory setting
3.0 [s]
Access level: 3
Func. diagram: 9795
Unit selection: -
Expert list: 1
Factory setting
30.0 [s]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
Switch off
ON
No acknowledgment
Leaked liquid
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1
SINAMICS G130/G150