Siemens G130 List Manual page 614

Hide thumbs Also See for G130:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
r3674[0...n]
CO: VSM 10 V input 2 actual value / VSM inp 2 U_act
VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: -
Min
- [V]
Description:
Displays the actual value of the voltage measured at the 10 V input 2 of the Voltage Sensing Module (VSM).
Dependency:
Refer to: p3670
Note:
10 V input 2: Terminals X520.3 and X520.4
p3680
BI: Braking Module internal inhibit / BM int inhib
B_INF
Can be changed: T
Data type: Unsigned32 / Binary
P-Group: -
Not for motor type: -
Min
-
Description:
Sets the signal source to inhibit the internal Braking Module.
BI: p3680 = 1 signal:
The Braking Module is inhibited.
BI: p3680 = 0 signal:
The Braking Module is enabled.
Dependency:
Refer to: A06904
Caution:
When the Braking Module is inhibited, no energy can be dissipated in the braking resistor.
p3681
BI: Activating Braking Module internal DC link fast discharge / BM intDCdischg act
B_INF
Can be changed: T
Data type: Unsigned32 / Binary
P-Group: -
Not for motor type: -
Min
-
Description:
Sets the signal source to activate the DC link fast discharge for an internal braking module.
When the following conditions apply, the DC link fast discharge is started later with delay time (p3682):
- BI: p3681 = 1 signal.
- an external line contactor is opened via r0863.1 "energize contactor".
The DC link fast discharge is interrupted when the following conditions apply:
- BI: p3681 = 0 signal.
- ON command for the infeed.
Recommendation:
The DC link fast discharge should be activated if there is an external line contactor and is correctly interconnected
(r0863.1, p0860). If the DC link fast discharge is not activated together with an external line contactor, then faults can
occur when precharging (e.g. F30027).
Dependency:
Refer to: p3682
Refer to: F30027
Notice:
The parameter is only effective for Basic Line Modules with the internal Braking Module (this is valid for Basic Line
Modules with a power rating of less than 100 kW).
614
Calculated: -
Dyn. index: p0150
Unit group: -
Scaling: p2001
Max
- [V]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: 9880
Unit selection: -
Expert list: 1
Factory setting
- [V]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
SINAMICS G130/G150

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

SinamicsG150

Table of Contents