2 Parameters
2.2 List of parameters
p4102[0...23]
TM150 fault threshold/alarm threshold / TM150 F/A_thresh
TM150
Can be changed: U, T
Data type: Integer16
P-Group: -
Not for motor type: -
Min
-99 [°C]
Description:
Sets the fault threshold/alarm threshold for Terminal Module 150 (TM150).
For alarms (even indices [0, 2, 4 ... 22]), the following applies:
- the corresponding alarm is initiated, if the temperature actual value associated with a temperature channel exceeds
the associated alarm threshold (r4105[x] > p4102[2x]. In addition, the timer is started (p4103[x]).
- the alarm remains until the temperature actual value (r4105[x]) reaches or falls below the threshold value
(p4102[2x] - hysteresis (p4118[x]).
For faults (uneven indices [1, 3, 5 ... 23]), the following applies:
- the corresponding fault is initiated, if the temperature actual value associated with a temperature channel exceeds
the associated fault threshold (r4105[x] > p4102[2x+1] or the associated timer (p4103[x] has expired.
- the fault remains until the temperature actual value (r4105[x]) reaches or falls below the threshold value
(p4102[2x+1]) - hysteresis (p4118[x]) and the fault has been acknowledged.
Index:
[0] = Channel 0 alarm threshold (A35211)
[1] = Channel 0 fault threshold (F35207)
[2] = Channel 1 alarm threshold (A35212)
[3] = Channel 1 fault threshold (F35208)
[4] = Channel 2 alarm threshold (A35213)
[5] = Channel 2 fault threshold (F35209)
[6] = Channel 3 alarm threshold (A35214)
[7] = Channel 3 fault threshold (F35210)
[8] = Channel 4 alarm threshold (A35410)
[9] = Channel 4 fault threshold (F35400)
[10] = Channel 5 alarm threshold (A35411)
[11] = Channel 5 fault threshold (F35401)
[12] = Channel 6 alarm threshold (A35412)
[13] = Channel 6 fault threshold (F35402)
[14] = Channel 7 alarm threshold (A35413)
[15] = Channel 7 fault threshold (F35403)
[16] = Channel 8 alarm threshold (A35414)
[17] = Channel 8 fault threshold (F35404)
[18] = Channel 9 alarm threshold (A35415)
[19] = Channel 9 fault threshold (F35405)
[20] = Channel 10 alarm threshold (A35416)
[21] = Channel 10 fault threshold (F35406)
[22] = Channel 11 alarm threshold (A35417)
[23] = Channel 11 fault threshold (F35407)
Dependency:
Refer to: p4103, r4104, r4105, p4118
Notice:
Faults F35207 ... F35210 and F35400 ... F35407 only result in the drive being shut down if at least one BICO
interconnection exists between the drive and the TM150.
For p4102[0...23] = 251 °C, evaluation of the corresponding threshold is deactivated.
For sensor type "PTC thermistor" (p4100[0...11] = 1), the following applies:
To activate the corresponding alarm or fault, p4102[0...23] must be set <= 250 °C.
Note:
The hysteresis can be set in p4118[0...11].
670
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
251 [°C]
List Manual (LH2), 07/2016, A5E03263479A
Access level: 1
Func. diagram: 9626, 9627
Unit selection: -
Expert list: 1