2 Parameters
2.2 List of parameters
p0287[0...1]
Ground fault monitoring threshold / Gnd flt threshold
VECTOR_G
Can be changed: T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
0.0 [%]
Description:
Sets the shutdown thresholds for the ground fault monitoring.
The setting is made as a percentage of the maximum current of the power unit (r0209).
Index:
[0] = Reduced at the start of precharging
[1] = Regular
Dependency:
Refer to: F30021
Note:
The parameter only applies to booksize and chassis power units.
Deactivating the ground fault monitoring:
- Sequence: --> p0287[1] = 0 --> p0287[0] = 0
- irrespective of the firmware version of the power unit.
Sets the thresholds:
- the prerequisite is at least firmware version 2.2 of the power unit.
r0289
CO: Maximum power unit output current / PU I_outp max
VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Displays, signals
Not for motor type: -
Min
- [Arms]
Description:
Displays the actual maximum output current of the power unit taking into account derating factors.
p0290
Power unit overload response / PU overld response
VECTOR_G
Can be changed: T
Data type: Integer16
P-Group: Converter
Not for motor type: -
Min
0
Description:
Sets the response to a thermal overload condition of the power unit.
The following quantities can result in a response to thermal overload:
- heat sink temperature (r0037[0]).
- chip temperature (r0037[1]).
- power unit overload I2t (r0036).
Possible measures to avoid thermal overload:
- reduce the output current limit r0289 and r0067 (for closed-loop speed/velocity or torque/force control) or the output
frequency (for U/f control) indirectly via the output current limit and the intervention of the current limiting controller).
- reduce the pulse frequency.
A reduction, if parameterized, is always realized after an appropriate alarm is output.
Value:
0:
1:
2:
3:
10:
12:
13:
126
Reduce output current
No reduction shutdown when overload threshold is reached
Reduce the pulse frequency and output current
Reduce the pulse frequency
Automatic output current reduction
Automatic pulse frequency and output current reduction
Automatic pulse frequency reduction
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
100.0 [%]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: p2002
Max
- [Arms]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
13
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
[0] 6.0 [%]
[1] 16.0 [%]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
- [Arms]
Access level: 3
Func. diagram: 8021
Unit selection: -
Expert list: 1
Factory setting
0
SINAMICS G130/G150