Siemens G130 List Manual page 150

Hide thumbs Also See for G130:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
p0363[0...n]
Motor saturation characteristic flux 2 / Mot saturat.flux 2
VECTOR_G
Can be changed: C2(3), U, T
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: RESM
Min
10.0 [%]
Description:
The saturation characteristic (flux as mapping of current) is defined using 4 points.
This parameter specifies the y coordinate (flux) for the 2nd value pair of the characteristic.
Induction motors (ASM) and separately excited synchronous motors (SESM):
The saturation characteristic describes the mapping of the magnetizing current onto the motor flux.
The parameter sets the second motor flux as a [%] referred to the rated motor flux.
Permanent magnet synchronous motors (PMSM):
The saturation characteristic describes the mapping of the stator quadrature axis current onto the stator quadrature
axis flux.
The parameter sets the second stator quadrature axis flux as a [%] referred to the product of the unsaturated
quadrature inductance (p0356) and the rated motor current.
Dependency:
The following applies for the flux values:
p0362 < p0363 < p0364 < p0365
The following applies for the stator quadrature axis flux values (PMSM):
20 % < p0362 < p0363 < p0364 < p0365
Refer to: p0367
Notice:
For permanent magnet synchronous motors (PMSM):
If the parameters are not set as specified, i.e. not in ascending order and to more than 20 %, the unsaturated
quadrature inductance (p0356) is always used for quadrature axis flux calculation purposes.
Note:
For induction motors, p0363 = 100 % corresponds to the rated motor flux.
For separately excited synchronous motors p0363 = 100% corresponds to an induced terminal voltage with the
magnitude of the rated motor voltage (under no-load conditions at the synchronous speed).
With permanent-magnet synchronous motors, p0362 = 100 % corresponds to the product of the unsaturated
quadrature inductance (p0356) and the rated motor current (p0305).
When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (p0300).
p0364[0...n]
Motor saturation characteristic flux 3 / Mot saturat.flux 3
VECTOR_G
Can be changed: C2(3), U, T
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: RESM
Min
10.0 [%]
Description:
The saturation characteristic (flux as mapping of current) is defined using 4 points.
This parameter specifies the y coordinate (flux) for the 3rd value pair of the characteristic.
Induction motors (ASM) and separately excited synchronous motors (SESM):
The saturation characteristic describes the mapping of the magnetizing current onto the motor flux.
The parameter sets the third motor flux as a [%] referred to the rated motor flux.
Permanent magnet synchronous motors (PMSM):
The saturation characteristic describes the mapping of the stator quadrature axis current onto the stator quadrature
axis flux.
The parameter sets the third stator quadrature axis flux as a [%] referred to the product of the unsaturated quadrature
inductance (p0356) and the rated motor current.
150
Calculated: -
Dyn. index: MDS, p0130
Unit group: -
Scaling: -
Max
800.0 [%]
Calculated: -
Dyn. index: MDS, p0130
Unit group: -
Scaling: -
Max
800.0 [%]
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: 6723, 6726
Unit selection: -
Expert list: 1
Factory setting
85.0 [%]
Access level: 3
Func. diagram: 6723, 6726
Unit selection: -
Expert list: 1
Factory setting
115.0 [%]
SINAMICS G130/G150

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

SinamicsG150

Table of Contents