2 Parameters
2.2 List of parameters
p0327[0...n]
Optimum motor load angle / Mot phi_load opt
VECTOR_G
Can be changed: C2(3), U, T
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: ASM, SESM, RESM
Min
0.0 [°]
Description:
Sets the optimum load angle for synchronous motors with reluctance torque (e.g. 1FE motors).
SERVO: The load angle is measured at 1.5 x rated motor current.
VECTOR: The load angle is measured at the rated motor current.
Notice:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note:
This parameter has no significance for induction motors.
For synchronous motors without reluctance torque, a angle of 90 degrees must be set.
When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (p0300).
p0328[0...n]
Motor reluctance torque constant / Mot kT_reluctance
VECTOR_G
Can be changed: C2(3), U, T
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: ASM, SESM, REL,
RESM
Min
-1000.00 [mH]
Description:
Sets the reluctance torque constant for synchronous motors with reluctance torque (e.g. 1FE ... motors).
This parameter has no significance for induction motors.
Notice:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note:
For synchronous motors without reluctance torque, the value 0 must be set.
p0329[0...n]
Motor pole position identification current / Mot PolID current
VECTOR_G
Can be changed: C2(3), U, T
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: ASM, SESM, REL
Min
0.00 [Arms]
Description:
Sets the current for the pole position identification routine (p1980 = 1).
For a two-stage technique (p1980 = 4), the current is set here for the 2nd phase.
The current of the 1st phase is set in p0325.
Dependency:
The following applies for vector drives:
If a maximum current (p0323) was not parameterized, then p0329 is limited to the rated motor current.
Refer to: p0325, p1980, p1982, r1984, r1985, r1987, p1990
Notice:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
138
Calculated: -
Dyn. index: MDS, p0130
Unit group: -
Scaling: -
Max
135.0 [°]
Calculated: -
Dyn. index: MDS, p0130
Unit group: -
Scaling: -
Max
1000.00 [mH]
Calculated: -
Dyn. index: MDS, p0130
Unit group: -
Scaling: -
Max
10000.00 [Arms]
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: 5722, 6721
Unit selection: -
Expert list: 1
Factory setting
90.0 [°]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0.00 [mH]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0.00 [Arms]
SINAMICS G130/G150