2 Parameters
2.2 List of parameters
p1285[0...n]
Vdc_min controller switch-in level (kinetic buffering) (U/f) / Vdc_min on_level
VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Functions
Not for motor type: -
Min
65 [%]
Description:
Sets the switch-in level for the Vdc-min controller (kinetic buffering).
The value is obtained as follows:
AC/AC device: r1286[V] = p1285[%] * sqrt(2) * p0210
DC/AC device: r1286[V] = p1285[%] * p0210
Warning:
An excessively high value may adversely affect normal drive operation. The values up to 150 % are intended for
operating modes p1240 = 5, 6.
r1286
Vdc_min controller switch-in level (kinetic buffering) (U/f) / Vdc_min on_level
VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Functions
Not for motor type: -
Min
- [V]
Description:
Displays the switch-in level for the Vdc_min controller (kinetic buffering).
Note:
The Vdc_min controller is not switched back off until the DC link voltage rises above the threshold 1.05 * r1286 and
the controller output is zero.
p1287[0...n]
Vdc_min controller dynamic factor (kinetic buffering) (U/f) / Vdc_min dyn_factor
VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Functions
Not for motor type: -
Min
1 [%]
Description:
Sets the dynamic factor for the Vdc_min controller (kinetic buffering).
100% means that p1290, p1291, and p1292 (gain, integral time, and rate time) are used corresponding to their basic
settings and based on a theoretical controller optimization.
If subsequent optimization is required, this can be carried out using the dynamic factor. In this case, p1290, p1291,
and p1292 are weighted with the dynamic factor p1287.
If several modules are connected to the DC link, then the dynamic factor must be increased corresponding to the
ratio of the additional capacitances to the capacitance of the module involved.
Note:
The pre-setting of the dynamic factor is based on the power units connected to DRIVE-CLiQ. It is assumed that the
power units connected via DRIVE-CLiQ are also electrically connected to the DC link. If this is not the case, then the
dynamic factor must be optimized manually.
p1288[0...n]
Vdc_max controller feedback coupling factor ramp-fct. gen. (U/f) /
Vdc_max factor RFG
VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Functions
Not for motor type: -
Min
0.000
Description:
Sets the feedback factor for the ramp-function generator.
Its ramp times are decelerated relative to the output signal of the Vdc_max controller.
368
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
150 [%]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: p2001
Max
- [V]
Calculated: CALC_MOD_CON
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
10000 [%]
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
100.000
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
76 [%]
Access level: 3
Func. diagram: 6320
Unit selection: -
Expert list: 1
Factory setting
- [V]
Access level: 3
Func. diagram: 6320
Unit selection: -
Expert list: 1
Factory setting
100 [%]
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0.500
SINAMICS G130/G150