2 Parameters
2.2 List of parameters
For U/f control and sensorless vector control, flying restart is not carried out (refer to p1200).
Refer to: r0192, p1900, p1910, p1960, p1990
Refer to: A07825, F07826
Notice:
In simulation mode, binector output r0863.1 = 1 is set. This is why you need to check whether other devices are
switched on via this signal before activating simulation mode. You might need to disconnect the corresponding BICO
interconnection temporarily.
Note:
Simulation mode is only possible for DC link voltages below 40 V. In order that the closed-loop control can be
calculated, the displayed DC link voltage (r0026, r0070) is set to the rated DC link voltage (refer to p0210). Closed-
loop current control and motor model are switched out (disabled) - the same is true for the speed controller for
encoderless closed-loop speed control.
When fault messages occur, the parameter is not automatically reset. This function is not implemented for
SINAMICS GM.
p1274[0...1]
Bypass switch monitoring time / Switch t_monit
VECTOR_G
Can be changed: U, T
(Tech_ctrl)
Data type: FloatingPoint32
P-Group: -
Not for motor type: RESM
Min
0 [ms]
Description:
Sets the monitoring time for the bypass switch.
Index:
[0] = Switch motor/drive
[1] = Switch motor/line supply
Note:
The monitoring is deactivated with p1274 = 0 ms.
The changeover time for the bypass (p1262) is extended by the value in this parameter.
p1275
Motor holding brake control word / Brake STW
VECTOR_G (Ext
Can be changed: U, T
brake)
Data type: Unsigned32
P-Group: Functions
Not for motor type: -
Min
-
Description:
Sets the control word for the motor holding brake.
Bit field:
Bit
00
01
02
03
05
06
Note:
For p1275.6 = 1 and p1275.5 = 1, the following applies:
The pulse enable (BO: r1229.3) is independent of the timer that has been set (p1217, p1216). The particular enable
is only defined by the feedback signal (BI: p1222, BI: p1223). The timers (p1216, p1217) only influence the alarm
A07931 "Brake does not open" and A07932 "Brake does not close".
364
Signal name
Inversion BI: 1219[0]
Inversion BI: 1219[1]
Inversion BI: 1224[0]
Inversion BI: 1224[1]
Brake with feedback
Enable with feedback signal
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
5000 [ms]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
List Manual (LH2), 07/2016, A5E03263479A
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1000 [ms]
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0000 0000 bin
0 signal
No
No
No
No
No
No
SINAMICS G130/G150
FP
2707
2707
2704
2704
2711
2711

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

SinamicsG150

Table of Contents