2 Parameters
2.2 List of parameters
r8843.0...2
BO: IF2 PZD state / IF2 PZD state
CU_G130_PN,
Can be changed: -
CU_G150_PN,
Data type: Unsigned8
CU_G130_DP,
P-Group: Communications
CU_G150_DP
Not for motor type: -
Min
-
Description:
Displays the PROFIdrive PZD state.
Bit field:
Bit
00
01
02
Dependency:
Refer to: p2044
Note:
When using the "setpoint failure" signal, the bus can be monitored and an application-specific response triggered
when the setpoint fails.
p8844
IF2 fault delay / IF2 F delay
VECTOR_G, B_INF,
Can be changed: U, T
ENC
Data type: FloatingPoint32
P-Group: Communications
Not for motor type: -
Min
0 [s]
Description:
Sets the delay time to initiate fault F01910 after a setpoint failure.
The time until the fault is initiated can be used by the application. This means that is is possible to respond to the
failure while the drive is still operational (e.g. emergency retraction).
Dependency:
Refer to: r2043
p8848
IF2 PZD sampling time / IF2 PZD t_sample
CU_G130_PN,
Can be changed: C1(3)
CU_G150_PN,
Data type: FloatingPoint32
CU_G130_DP,
P-Group: Communications
CU_G150_DP
Not for motor type: -
Min
1.00 [ms]
Description:
Sets the sampling time for the cyclic interface 2 (IF2).
Note:
The system only permits certain sampling times and after writing to this parameter, displays the value that has
actually been set.
For clock cycle synchronous operation, the specified bus cycle time applies (Tdp).
r8849[0...139]
COMM BOARD receive configuration data / CB r config_dat
CU_G130_PN (COMM
Can be changed: -
BOARD, PN CBE20),
Data type: Unsigned16
CU_G150_PN (COMM
P-Group: Communications
BOARD, PN CBE20),
Not for motor type: -
CU_G130_DP (COMM
BOARD, PN CBE20),
Min
CU_G150_DP (COMM
-
BOARD, PN CBE20)
Description:
Displays the receive configuration data for the COMM BOARD.
842
Signal name
Setpoint failure
Clock cycle synchronous operation active
Fieldbus oper
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
1 signal
Yes
Yes
Yes
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
100 [s]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
16.00 [ms]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: 2410
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
No
No
No
Access level: 3
Func. diagram: 2410
Unit selection: -
Expert list: 1
Factory setting
0 [s]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
4.00 [ms]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
SINAMICS G130/G150
FP
-
-
-