For bit 01:
When the bit is set, the I component of the speed controller is kept when changing into the open-loop controlled
mode.
For bit 16:
When the bit is set, the integral component of the speed controller is only held if it reaches the torque limit.
For bit 19:
When this bit is set, speed overshoots when accelerating along the torque limit and for load surges are reduced. If
the setpoint torque reaches the torque limit, then the integral component is set to the difference between the torque
limit and P component.
For bits 20, 23:
The acceleration model for the speed setpoint is only active if p1496 is not zero. When the acceleration model and
the ramp-function generator (p1145) are simultaneously activated, it is recommended that p1400 bit 16 is set (this
allows the I component to run freely up to the torque limit).
For bit 24:
When the bit is set, assuming that the motor accelerates smoothly, the moment of inertia can be determined faster.
For bit 25:
When the bit is set, for high dynamic starting in the I/f mode, the acceleration precontrol torque smoothing only has a
short minimum time (4 ms).
p1401[0...n]
Flux control configuration / Flux ctrl config
VECTOR_G (n/M)
Can be changed: U, T
Data type: Unsigned16
P-Group: Closed-loop control
Not for motor type: REL
Min
-
Description:
Sets the configuration for flux setpoint control
Bit field:
Bit
00
01
02
03
04
05
06
07
08
09
10
13
Note:
For bit 00 (only for induction motors):
Initially, the flux is only established with a low rate of rise when magnetizing the induction motor. The flux setpoint
p1570 is reached again at the end of the magnetizing time p0346.
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Obtain moment of inertia estimator value for
pulse inhibit
Acceleration model (with speed encoder)
Accelerated moment of inertia estimator
active
Acceleration torque instantaneous in the I/f
mode
Signal name
Flux setpoint soft starting active
Flux setpoint differentiation active
Flux build-up control active
Flux characteristic load-dependent
Flux controller (ASM with encoder)
Flux impression (ASM with encoder)
Quick magnetizing
Pre-control speed limitation
Speed limiting controller
Dynamic load-dependent flux boost
Flux boost low speed
Precontrol characteristic (PESM)
Yes
Yes
Yes
Yes
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
with model chngov
Yes
Yes
With M_limits
Yes
Yes
Yes
2 Parameters
2.2 List of parameters
No
No
No
No
Access level: 3
Func. diagram: 6491
Unit selection: -
Expert list: 1
Factory setting
0000 0000 0000 1110 bin
0 signal
No
No
No
No
No
From 30 % n_rated
No
No
With I_limits
No
No
No
6030
6030
6030
-
FP
6722,
6725
6723,
6726
6722,
6723,
6725,
6726
6725
-
-
6722
6640
6640
6790,
6823
6790,
6823
-
385

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

SinamicsG150

Table of Contents