3008: 2048 TTL A/B
3009: 1024 HTL A/B unipolar
3011: 2048 HTL A/B unipolar
3020: 2048 TTL A/B R, with sense
9999: User-defined
10000: Identify encoder
Notice:
An encoder type with p0400 < 9999 defines an encoder for which there is an encoder parameter list.
When selecting a catalog encoder (p0400 < 9999) the parameters from the encoder parameter list cannot be
changed (write protection). To remove write protection, the encoder type should be set to a third-party encoder
(p0400 = 9999).
Note:
The connected encoder can be identified by setting p0400 to 10000 or 10100. This assumes that the encoder
supports this method, which is possible in the following cases: Motor with DRIVE-CLiQ, encoder with EnDat
interface, DRIVE-CLiQ encoder, encoder with SSI interface (only 10100)..
The encoder data (e.g. pulse number p0408) can only be changed when p0400 = 9999.
When using an encoder with track A/B and zero pulse, as standard, fine synchronization is not set using a zero mark.
If, for a synchronous motor, fine synchronization is to be realized using a zero mark, then the following must be
executed:
- set p0400 to 9999
- set p0404.15 to 1
Prerequisite:
Coarse synchronization must be selected (e.g. pole position identification) and the zero pulse of the encoder must be
either mechanically or electronically (p0431) adjusted to the pole position.
For p0400 = 10000 the following applies:
If an identification is not possible, then p0400 is set to 0.
For p0400 = 10100 the following applies:
If an identification is not possible, p0400 remains set to 10100 until it becomes possible.
p0400[0...n]
Encoder type selection / Enc_typ sel
ENC
Can be changed: C2(1, 4)
Data type: Integer16
P-Group: Encoder
Not for motor type: -
Min
0
Description:
Selects the encoder from the list of encoder types supported.
Value:
0:
202:
204:
242:
244:
1001: Resolver 1 speed
1002: Resolver 2 speed
1003: Resolver 3 speed
1004: Resolver 4 speed
2001: 2048, 1 Vpp, A/B C/D R
2002: 2048, 1 Vpp, A/B R
2003: 256, 1 Vpp, A/B R
2004: 400, 1 Vpp, A/B R
2005: 512, 1 Vpp, A/B R
2006: 192, 1 Vpp, A/B R
2007: 480, 1 Vpp, A/B R
2008: 800, 1 Vpp, A/B R
2010: 18000, 1 Vpp, A/B R distance-coded
2012: 420, 1 Vpp, A/B R
2013: 675, 1 Vpp, A/B R
2051: 2048, 1 Vpp, A/B, EnDat, Multiturn 4096
2052: 32, 1 Vpp, A/B, EnDat, Multiturn 4096
2053: 512, 1 Vpp, A/B, EnDat, Multiturn 4096
2054: 16, 1 Vpp, A/B, EnDat, Multiturn 4096
2055: 2048, 1 Vpp, A/B, EnDat, Singleturn
2081: 2048, 1 Vpp, A/B, SSI, Singleturn
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
No encoder
DRIVE-CLiQ encoder AS20, singleturn
DRIVE-CLiQ encoder AM20, multiturn 4096
DRIVE-CLiQ encoder AS24, singleturn
DRIVE-CLiQ encoder AM24, multiturn 4096
Calculated: -
Dyn. index: EDS, p0140
Unit group: -
Scaling: -
Max
10100
2 Parameters
2.2 List of parameters
Access level: 1
Func. diagram: 4700, 4704
Unit selection: -
Expert list: 1
Factory setting
0
161