2 Parameters
2.2 List of parameters
Dependency:
Refer to: p0860, r0863
Refer to: F07300
Note:
The monitoring function is disabled for the factory setting of p0860.
p0862
Power unit ON delay / PU t_on
VECTOR_G, B_INF
Can be changed: T
Data type: FloatingPoint32
P-Group: Commands
Not for motor type: -
Min
0 [ms]
Description:
Sets the delay time for the control command of the power unit and a line contactor, if used.
Note:
This means that it is possible to realize a shifted (delayed) precharging or switch-on using a single ON command.
When the infeed units are active, before the line contactor is closed, an offset adjustment of the current measurement
is carried out for a duration of 120 ms (p3491).
r0863.0...2
CO/BO: Drive coupling status word/control word / CoupleZSW/STW
VECTOR_G, B_INF
Can be changed: -
Data type: Unsigned16
P-Group: Commands
Not for motor type: -
Min
-
Description:
Display and BICO output for the status word and control word of the drive coupling.
Bit field:
Bit
00
01
02
Dependency:
Refer to: p0864
Note:
For bit 00:
Bit 0 signals that the infeed is ready.
When the operating signal is transferred via binector output r0863.0 this allows several drives to start (run-up)
staggered over time when they are simultaneously switched on.
To realize this, the following connections/interconnections are required:
Drive 1: Interconnect binector input p0864 with binector output r0863.0 of the infeed
Drive 2: Interconnect binector input p0864 with binector output r0863.0 of drive 1
Drive 3: Interconnect binector input p0864 with binector output r0863.0 of drive 2 etc.
The first drive only transfers the operating signal to the next drive after it has reached its ready condition.
For bit 01:
Bit 1 is used to control an external line contactor.
For bit 02:
This bit only signals line supply failure for Active Infeed (A_INF) and Smart Infeed (S_INF).
282
Signal name
Closed-loop control operation
Energize contactor
Infeed line supply failure
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
65000 [ms]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
1 signal
Yes
Yes
Yes
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: 2610, 8732,
8832, 8932
Unit selection: -
Expert list: 1
Factory setting
0 [ms]
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
No
No
No
SINAMICS G130/G150
FP
2610,
8710,
8810,
8910
2610,
2634,
7990,
8734,
8834,
8934
-