p3326[0...n]
Fluid flow machine power point 4 / Fluid_mach P4
VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Displays, signals
Not for motor type: -
Min
0.00
Description:
For the energy-saving display of a fluid-flow machine, a typical flow characteristic P = f(n) with 5 points along the
characteristic is required.
This parameter specifies the power (P) of point 4 as a [%].
Dependency:
Refer to: r0041, p3320, p3321, p3322, p3323, p3324, p3325, p3327, p3328, p3329
Note:
The reference value for power and speed is the rated power/rated speed.
The energy saved is displayed in r0041.
p3327[0...n]
Fluid flow machine speed point 4 / Fluid_mach n4
VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Displays, signals
Not for motor type: -
Min
0.00
Description:
For the energy-saving display of a fluid-flow machine, a typical flow characteristic P = f(n) with 5 points along the
characteristic is required.
This parameter specifies the speed (n) of point 4 as a [%].
Dependency:
Refer to: r0041, p3320, p3321, p3322, p3323, p3324, p3325, p3326, p3328, p3329
Note:
The reference value for power and speed is the rated power/rated speed.
The energy saved is displayed in r0041.
p3328[0...n]
Fluid flow machine power point 5 / Fluid_mach P5
VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Displays, signals
Not for motor type: -
Min
0.00
Description:
For the energy-saving display of a fluid-flow machine, a typical flow characteristic P = f(n) with 5 points along the
characteristic is required.
This parameter specifies the power (P) of point 5 as a [%].
Dependency:
Refer to: r0041, p3320, p3321, p3322, p3323, p3324, p3325, p3326, p3327, p3329
Note:
The reference value for power and speed is the rated power/rated speed.
The energy saved is displayed in r0041.
p3329[0...n]
Fluid flow machine speed point 5 / Fluid_mach n5
VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Displays, signals
Not for motor type: -
Min
0.00
Description:
For the energy-saving display of a fluid-flow machine, a typical flow characteristic P = f(n) with 5 points along the
characteristic is required.
This parameter specifies the speed (n) of point 5 as a [%].
Dependency:
Refer to: r0041, p3320, p3321, p3322, p3323, p3324, p3325, p3326, p3327, p3328
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
100.00
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
100.00
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
100.00
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
100.00
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
92.00
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
75.00
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
100.00
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
100.00
605