r9894[2] = 3 (F-DI changeover, tolerance time)
...
The complete list of numbers for crosswise data comparison is listed in Fault F30611.
r9895
SI diagnostics STOP F (Motor Module) / SI diag STOP F MM
VECTOR_G
Can be changed: -
Data type: Unsigned32
P-Group: Safety Integrated
Not for motor type: -
Min
-
Description:
Displays the number of the cross-compared data, which has caused STOP F on the Motor Module/Hydraulic Module.
Dependency:
Refer to: r9795
Refer to: F30611
Note:
The complete list of numbers for crosswise data comparison is listed in Fault F30611.
p9897
SI Motion bus failure STO delay time (MM) / SI Mtn IL t_del MM
VECTOR_G
Can be changed: C2(95)
Data type: FloatingPoint32
P-Group: Safety Integrated
Not for motor type: -
Min
0.00 [µs]
Description:
Sets the delay time for STO after bus failure on the Motor Module/Hydraulic Module (e.g. used for ESR).
Notice:
This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note:
Rounding effects can occur in the last decimal place of the parameterized time. The set time is rounded internally to
an integer multiple of the monitoring clock cycle.
ESR: Extended Stop and Retract
STO: Safe Torque Off / SH: Safe standstill
r9898
SI actual checksum SI parameters (Motor Module) / SI act_checksum MM
VECTOR_G
Can be changed: -
Data type: Unsigned32
P-Group: Safety Integrated
Not for motor type: -
Min
-
Description:
Displays the checksum for the checked Safety Integrated parameters on the Motor Module/Hydraulic Module (actual
checksum).
Dependency:
Refer to: r9798, p9899
p9899
SI reference checksum SI parameters (Motor Module) / SI set_checksum MM
VECTOR_G
Can be changed: C2(95)
Data type: Unsigned32
P-Group: Safety Integrated
Not for motor type: -
Min
0000 hex
Description:
Sets the checksum for the checked Safety Integrated parameters on the Motor Module/Hydraulic Module (reference
checksum).
Dependency:
Refer to: p9799, r9898
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
800000.00 [µs]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
FFFF FFFF hex
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: 2802
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0.00 [µs]
Access level: 3
Func. diagram: 2800
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: 2800
Unit selection: -
Expert list: 1
Factory setting
0000 hex
1011