Siemens G130 List Manual page 1053

Hide thumbs Also See for G130:
Table of Contents

Advertisement

264:
265:
266:
267:
268:
269:
270:
271:
513:
514:
515:
516:
517:
518:
519:
520:
521:
522:
523:
524:
525:
526:
527:
769:
770:
771:
772:
773:
774:
775:
776:
777:
778:
779:
780:
781:
782:
783:
Index:
[0] = AND logic operation input 1
[1] = AND logic operation input 2
[2] = AND logic operation input 3
[3] = AND logic operation input 4
[4] = AND logic operation input 5
[5] = AND logic operation input 6
Note:
F-DO: Failsafe Digital Output
p10045[0...5]
SI TM54F F-DO 3 signal sources / SI F-DO 3 S_src
TM54F_MA,
Can be changed: C2(95)
TM54F_SL
Data type: Integer16
P-Group: Safety Integrated
Not for motor type: -
Min
0
Description:
Sets the signal sources for F-DO 3.
The 6 signal sources in p10045[0...5] are AND'ed and the result is output at F-DO 3.
Value:
0:
1:
2:
3:
4:
5:
6:
7:
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Drive group 2 SOS selected
Drive group 2 internal event
Drive group 2 active SLS stage bit 0
Drive group 2 active SLS stage bit 1
Drive group 2 SDI positive active
Drive group 2 SDI negative active
Drive group 2 SLP active
Drive group 2 active SLP area
Drive group 3 STO active
Drive group 3 SS1 active
Drive group 3 SS2 active
Drive group 3 SOS active
Drive group 3 SLS active
Drive group 3 SSM feedback signal active
Drive group 3 safe state
Drive group 3 SOS selected
Drive group 3 internal event
Drive group 3 active SLS stage bit 0
Drive group 3 active SLS stage bit 1
Drive group 3 SDI positive active
Drive group 3 SDI negative active
Drive group 3 SLP active
Drive group 3 active SLP area
Drive group 4 STO active
Drive group 4 SS1 active
Drive group 4 SS2 active
Drive group 4 SOS active
Drive group 4 SLS active
Drive group 4 SSM feedback signal active
Drive group 4 safe state
Drive group 4 SOS selected
Drive group 4 internal event
Drive group 4 active SLS stage bit 0
Drive group 4 active SLS stage bit 1
Drive group 4 SDI positive active
Drive group 4 SDI negative active
Drive group 4 SLP active
Drive group 4 active SLP area
No function
Drive group 1 STO active
Drive group 1 SS1 active
Drive group 1 SS2 active
Drive group 1 SOS active
Drive group 1 SLS active
Drive group 1 SSM feedback signal active
Drive group 1 safe state
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
783
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 2902, 2907
Unit selection: -
Expert list: 1
Factory setting
0
1053

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

SinamicsG150

Table of Contents