Implementation:
MDS0: p0827[0] = 4, interconnect output to switch contactor 0 to r0830.4, p0831[4] = "input, feedback signal,
contactor 0"
MDS1: p0827[1] = 5, interconnect output to switch contactor 1 to r0830.5, p0831[5] = "input, feedback signal,
contactor 1"
The following sequence applies when changing over from MDS0 to MDS1:
1. Status bit r0830.4 is deleted. When the feedback signal (p0831[4]) is connected, the system waits until the
feedback signal "contactor open" is displayed. If the feedback signal is not connected, then the system waits for the
switch-off interlocking time of 320 ms.
2. Status bit r0830.5 is set. If the feedback signal (p0831[5]) is connected, the system waits until the feedback signal
"contactor closed" is displayed. If the feedback signal is not connected, then the system waits for the switch-on
interlocking time of 160 ms.
Index:
[0] = Feedback signal contactor 0
[1] = Feedback signal contactor 1
[2] = Feedback signal contactor 2
[3] = Feedback signal contactor 3
[4] = Feedback signal contactor 4
[5] = Feedback signal contactor 5
[6] = Feedback signal contactor 6
[7] = Feedback signal contactor 7
[8] = Feedback signal contactor 8
[9] = Feedback signal contactor 9
[10] = Feedback signal contactor 10
[11] = Feedback signal contactor 11
[12] = Feedback signal contactor 12
[13] = Feedback signal contactor 13
[14] = Feedback signal contactor 14
[15] = Feedback signal contactor 15
r0832.0...15
CO/BO: Mot. changeover contactor feedback sig. status word / Mot_chng fdbk ZSW
VECTOR_G
Can be changed: -
Data type: Unsigned32
P-Group: Displays, signals
Not for motor type: -
Min
-
Description:
Displays the status word of the contactor feedback signals when changing over a motor.
Bit field:
Bit
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
Dependency:
Refer to: p0831
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Signal name
Feedback signal contactor 0
Feedback signal contactor 1
Feedback signal contactor 2
Feedback signal contactor 3
Feedback signal contactor 4
Feedback signal contactor 5
Feedback signal contactor 6
Feedback signal contactor 7
Feedback signal contactor 8
Feedback signal contactor 9
Feedback signal contactor 10
Feedback signal contactor 11
Feedback signal contactor 12
Feedback signal contactor 13
Feedback signal contactor 14
Feedback signal contactor 15
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
1 signal
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: 8575
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
Opened
Opened
Opened
Opened
Opened
Opened
Opened
Opened
Opened
Opened
Opened
Opened
Opened
Opened
Opened
Opened
FP
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-