Siemens G130 List Manual page 476

Hide thumbs Also See for G130:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
17
20
22
23
24
25
Note:
The following applies to permanent-magnet synchronous motors:
Without de-selection in bit 11, in the closed-loop control mode, the direct inductance LD and the quadrature
inductance Lq are measured at a low current.
When de-selecting with bit 11 or in the U/f mode, the stator inductance is measured at half the rated motor current.
If the stator is inductance is not measured but is to be estimated, then bit 0 should be set and bit 11 should be de-
selected.
p1910
Motor data identification selection / MotID selection
VECTOR_G
Can be changed: T
Data type: Integer16
P-Group: Motor identification
Not for motor type: -
Min
0
Description:
Sets the motor data identification routine.
The motor data identification routine is carried out after the next switch-on command.
p1910 = 1:
All motor data and the drive converter characteristics are identified and then transferred to the following parameters:
p0350, p0354, p0356, p0357, p0358, p0360, p1825, p1828, p1829, p1830
After this, the control parameter p0340 = 3 is automatically calculated.
Value:
0:
1:
2:
3:
4:
5:
6:
7:
8:
9:
10:
20:
21:
22:
23:
24:
25:
26:
27:
28:
Dependency:
"Quick commissioning" must be carried out (p0010 = 1) before executing the motor data identification routine!
In the simulation mode, the parameter cannot be written into. When selecting the motor data identification routine, the
drive data set changeover is suppressed.
Refer to: p1272, p1900
Refer to: F07990, A07991
Notice:
After the motor data identification (p1910 > 0) has been selected, alarm A07991 is output and a motor data
identification routine is carried out as follows at the next switch-on command:
- current flows through the motor and a voltage is present at the drive converter output terminals.
- during the identification routine, the motor shaft can rotate through a maximum of half a revolution.
- however, no torque torque is generated.
476
Measurement without control parameter
calculation
Estimate cable resistance
Only identify circle
Deactivate circle identification
Circle identification with 0 and 90 degrees
Deactivate gating unit switchover
Inhibited
Complete identification (ID) and acceptance of motor data
Complete identification (ID) of motor data without acceptance
ID of the saturation characteristic and acceptance
ID of the saturation characteristic without acceptance
ID of dynamic leakage inductance Lsig (r1920) without acceptance
ID of lockout time (r1926) without acceptance
ID of stator resistance Rs (r1912) without acceptance
ID of stator inductance Ls (r1915) Rr (r1927) without acceptance
ID of rotor time constant Tr (r1913) without acceptance
ID of static leakage inductance Lsig (r1914) without acceptance
Voltage vector input
Voltage vector input without filter
Rectangular voltage vector input without filter
Triangular voltage vector input without filter
Rectangular voltage vector input with filter
Triangular voltage vector input with filter
Enter voltage vector with DTC correction
Enter voltage vector with AVC
Enter voltage vector with DTC + AVC correction
Yes
Yes
Yes
Yes
Yes
Yes
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
28
List Manual (LH2), 07/2016, A5E03263479A
No
No
No
No
No
No
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1
SINAMICS G130/G150
-
-
-
-
-
-