2 Parameters
2.2 List of parameters
p1961
Saturation characteristic speed to determine / Sat_char n determ
VECTOR_G (n/M)
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Motor identification
Not for motor type: REL
Min
26 [%]
Description:
Sets the speed to determine the saturation characteristic and the encoder test.
The percentage value is referred to p0310 (rated motor frequency).
Dependency:
Refer to: p0310, p1959
Refer to: F07983
Note:
The saturation characteristics should be determined at an operating point with the lowest possible load.
r1962[0...4]
Saturation characteristic magnetizing current / Sat_char I_mag
VECTOR_G (n/M)
Can be changed: -
Data type: FloatingPoint32
P-Group: Motor identification
Not for motor type: PMSM, REL
Min
- [%]
Description:
Displays the magnetizing currents of the identified saturation characteristic.
The values are referred to r0331.
After they have been determined, the values are transferred to p0366 ... p0369.
Index:
[0] = Value 1
[1] = Value 2
[2] = Value 3
[3] = Value 4
[4] = Value 5
Dependency:
Refer to: r0331
r1963[0...4]
Saturation characteristic magnetizing inductance / Sat_char L_main
VECTOR_G (n/M)
Can be changed: -
Data type: FloatingPoint32
P-Group: Motor identification
Not for motor type: PMSM, REL
Min
- [%]
Description:
Displays the magnetizing inductances of the identified saturation characteristic.
The values are referred to r0382.
Index:
[0] = Value 1
[1] = Value 2
[2] = Value 3
[3] = Value 4
[4] = Value 5
Dependency:
Refer to: r0382
484
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
75 [%]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
- [%]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
- [%]
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
40 [%]
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
- [%]
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
- [%]
SINAMICS G130/G150