2 Parameters
2.2 List of parameters
07
08
09
10
11
Dependency:
Refer to: r4105, r4112, r4113, r4114
Notice:
When forming groups, it must be ensured that in one particular group, only temperature channels with the following
sensor types are included:
- "KTY84", "PT100", "PT1000" (p4100[0...11] = 2, 5, 6), real temperature actual value
or alternatively
- "PTC thermistor", "bimetallic NC contact" (p4100[0...11] = 1, 4), fictitious temperature actual value (-50 °C, 250 °C)
If these sensor types are combined within one group, then the calculated values for maximum, minimum and average
value will be falsified.
Note:
Active and inactive temperature channels can be included in one group. However, when calculating the values
(r4112, r4113, r4114) only the active temperature channels with valid actual value are taken into account
(r4105[0...11] not equal to -300 °C).
r4112[0...2]
CO: TM150 group temperature actual value maximum value / TM150 grp temp max
TM150
Can be changed: -
Data type: FloatingPoint32
P-Group: Terminals
Not for motor type: -
Min
- [°C]
Description:
Display and connector output for the maximum value of each group for the Terminal Module 150 (TM150).
This value is calculated from the actual temperature values (r4105[0...11]) of each group.
Recommendation:
The following connector inputs can use these connector outputs for interconnection:
- CI: p0603
- CI: p0608[0...3]
- CI: p0609[0...3]
- CI: p2051
Index:
[0] = Group 0
[1] = Group 1
[2] = Group 2
Dependency:
Refer to: r4105, p4111, r4113, r4114
r4113[0...2]
CO: TM150 group temperature actual value minimum value / TM150 grp temp min
TM150
Can be changed: -
Data type: FloatingPoint32
P-Group: Terminals
Not for motor type: -
Min
- [°C]
Description:
Display and connector output for the minimum value of each group for the Terminal Module 150 (TM150).
This value is calculated from the actual temperature values (r4105[0...11]) of each group.
Recommendation:
The following connector inputs can use these connector outputs for interconnection:
- CI: p0603
- CI: p0608[0...3]
- CI: p0609[0...3]
- CI: p2051
Index:
[0] = Group 0
[1] = Group 1
[2] = Group 2
Dependency:
Refer to: r4105, p4111, r4112, r4114
678
Temperature channel 7
Temperature channel 8
Temperature channel 9
Temperature channel 10
Temperature channel 11
Yes
Yes
Yes
Yes
Yes
Calculated: -
Dyn. index: -
Unit group: -
Scaling: p2006
Max
- [°C]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: p2006
Max
- [°C]
List Manual (LH2), 07/2016, A5E03263479A
No
No
No
No
No
Access level: 1
Func. diagram: 9625
Unit selection: -
Expert list: 1
Factory setting
- [°C]
Access level: 1
Func. diagram: 9625
Unit selection: -
Expert list: 1
Factory setting
- [°C]
SINAMICS G130/G150
-
-
-
-
-