2 Parameters
2.2 List of parameters
Example:
The actual value of the total torque (r0079) is connected to a test socket (e.g. p0771[0]). The actual torque is
cyclically converted into a percentage of the reference torque (p2003) and output according to the parameterized
scaling.
r2004
Reference power / P_ref
VECTOR_G, B_INF
Can be changed: -
Data type: FloatingPoint32
P-Group: Communications
Not for motor type: -
Min
- [kW]
Description:
Displays the reference quantity for power.
All power ratings specified as relative value are referred to this reference quantity.
The reference quantity corresponds to 100% or 4000 hex (word) or 4000 0000 hex (double word).
Dependency:
This value is calculated as follows:
Infeed: Calculated from voltage times current.
Closed-loop control: Calculated from torque times speed.
Refer to: p2000, p2001, p2002, p2003
Note:
If a BICO interconnection is established between different physical quantities, then the particular reference quantities
are used as internal conversion factor.
The reference power is calculated as follows:
- 2 * Pi * reference speed / 60 * reference torque (motor)
- reference voltage * reference current * root(3) (infeed)
p2005
Reference angle / Reference angle
VECTOR_G, B_INF
Can be changed: T
Data type: FloatingPoint32
P-Group: Communications
Not for motor type: -
Min
90.00 [°]
Description:
Sets the reference quantity for angle.
All angles specified as relative value are referred to this reference quantity.
The reference quantity corresponds to 100% or 4000 hex (word) or 4000 0000 hex (double word).
Note:
For the automatic calculation (p0340 = 1, p3900 > 0) an appropriate pre-assignment is only made if the parameter is
not inhibited from being overwritten using p0573 = 1.
If a BICO interconnection is established between different physical quantities, then the particular reference quantities
are used as internal conversion factor.
p2006
Reference temp / Ref temp
VECTOR_G, B_INF,
Can be changed: T
TM31, TM120, TM150
Data type: FloatingPoint32
P-Group: Communications
Not for motor type: -
Min
50.00 [°C]
Description:
Sets the reference quantity for temperature.
All temperatures specified as relative value are referred to this reference quantity.
The reference quantity corresponds to 100% or 4000 hex (word) or 4000 0000 hex (double word).
494
Calculated: -
Dyn. index: -
Unit group: 14_10
Scaling: -
Max
- [kW]
Calculated: CALC_MOD_ALL
Dyn. index: -
Unit group: -
Scaling: -
Max
180.00 [°]
Calculated: CALC_MOD_ALL
Dyn. index: -
Unit group: -
Scaling: -
Max
300.00 [°C]
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: -
Unit selection: p0505
Expert list: 1
Factory setting
- [kW]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
90.00 [°]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
100.00 [°C]
SINAMICS G130/G150