2 Parameters
2.2 List of parameters
p7775
NVRAM data backup/import/delete / NVRAM backup
CU_G130_PN,
Can be changed: C1, U, T
CU_G150_PN,
Data type: Integer16
CU_G130_DP,
P-Group: All groups
CU_G150_DP
Not for motor type: -
Min
0
Description:
Setting to backup/import/delete NVRAM data.
NVRAM data are non-volatile data in the device (e.g. fault buffer).
For NVRAM data actions, the following data are excluded:
- crash diagnostics
- CU operating hours counter
- CU temperature
- safety logbook
Value:
0:
1:
2:
3:
10:
11:
12:
13:
14:
15:
16:
17:
Notice:
For value = 2, 3:
These actions are only possible when pulses are inhibited.
Note:
After the action has been successfully completed, the parameter is automatically set to zero.
The actions importing and deleting NVRAM data immediately initiate a warm restart.
If the procedure was not successfully completed, then an appropriate fault value is displayed (p7775 >= 10).
p7786[0...n]
Service report / Service report
VECTOR_G, B_INF
Can be changed: U, T
Data type: Unsigned16
P-Group: -
Not for motor type: -
Min
-
Description:
Service parameter to internally document repairs.
After a component has been replaced, this must be confirmed using p7786.x = 0/1.
When acknowledging a replacement, the "Generate report" function is automatically executed.
p7786.x is automatically set to 0 after POWER ON.
Bit field:
Bit
00
01
02
03
04
05
06
15
Notice:
This write process can take several minutes.
Note:
The power unit involved can be assigned the correct P index using p0124 (power unit detection via LED).
776
Inactive
NVRAM data backup to memory card
Import NVRAM data from the memory card
Delete NVRAM data in the device
Error when clearing
Error when backing up, memory card not available
Error when backing up, insufficient memory space
Error when backing up
Error when importing, memory card not available
Error when importing, checksum error
Error when importing, no NVRAM data available
Error when importing
Signal name
Control Interface Module (CIM) replaced
Valve 1 replaced
Valve 2 replaced
Valve 3 replaced
Valve 4 replaced
Valve 5 replaced
Valve 6 replaced
Generate report
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
17
Calculated: -
Dyn. index: PDS, p0120
Unit group: -
Scaling: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0000 0000 0000 0000 bin
0 signal
No
No
No
No
No
No
No
No