p3422
DC link capacitance total / C_DC tot
VECTOR_G
Can be changed: U, T
(Tech_ctrl)
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: -
Min
0.20 [mF]
Description:
Sets the total DC link capacitance for closed-loop voltage control.
The capacitance of one power unit is pre-assigned to this value. The value should be adapted according to the
number of power units.
Note:
The controller setting for the DC link voltage controller is derived from this value.
p3490
Infeed delay time OFF1 command / INF t_del OFF1
B_INF
Can be changed: T
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: -
Min
0.0 [ms]
Description:
Sets the delay time for the ON/OFF1 command of the infeed.
After ON/OFF1 = 0 the infeed remains in operation for the specified time
Dependency:
Refer to: p0840
Notice:
The ON/OFF1 command of the infeed can be interrupted.
Note:
This parameter is only relevant if a Motor Module and the infeed are controlled by the same OFF command. In this
case, the delay time and the stop ramp time of the motor can be coordinated with one another.
p3510
DC link voltage setpoint / Vdc setp
VECTOR_G
Can be changed: U, T
(Tech_ctrl)
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: -
Min
100.00 [V]
Description:
Sets the setpoint for the DC link voltage on the motor side.
p3511
CI: DC link voltage supplementary setpoint / Vdc Z_set
VECTOR_G
Can be changed: T
(Tech_ctrl)
Data type: Unsigned32 / FloatingPoint32
P-Group: Closed-loop control
Not for motor type: -
Min
-
Description:
Sets the signal source for the supplementary setpoint for the DC link voltage on the motor side.
Dependency:
Refer to: p3510
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
2000.00 [mF]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
1000000.0 [ms]
Calculated: -
Dyn. index: -
Unit group: 5_2
Scaling: p2001
Max
1600.00 [V]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: p2001
Max
-
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
2.00 [mF]
Access level: 2
Func. diagram: 8732, 8832,
8932
Unit selection: -
Expert list: 1
Factory setting
0.0 [ms]
Access level: 2
Func. diagram: 7960
Unit selection: p0505
Expert list: 1
Factory setting
600.00 [V]
Access level: 3
Func. diagram: 7960
Unit selection: -
Expert list: 1
Factory setting
0
607