Siemens G130 List Manual page 927

Hide thumbs Also See for G130:
Table of Contents

Advertisement

Dependency:
Refer to: p9495, p9496, p9498, p9499
Refer to: A01318, A01507
p9498[0...29]
BICO BI/CI parameters to deactivated drive objects / BI/CI to deact obj
CU_G130_PN,
Can be changed: T
CU_G150_PN,
Data type: Unsigned32
CU_G130_DP,
P-Group: Commands
CU_G150_DP,
Not for motor type: -
VECTOR_G, B_INF,
TM31, TM120, TM150,
Min
TB30, ENC
-
Description:
Displays the saved BI/CI parameters (signal sink), whose source is located on drive objects that are either not
capable of operation or have been deactivated.
Dependency:
Refer to: p9495, p9496, p9497, p9499
Refer to: A01318, A01507
Note:
A BICO interconnection (signal sink, signal source) is displayed in the same index of p9498 and p9499.
p9499[0...29]
BICO BO/CO parameters to deactivated drive objects / BO/CO to deact obj
CU_G130_PN,
Can be changed: T
CU_G150_PN,
Data type: Unsigned32
CU_G130_DP,
P-Group: Commands
CU_G150_DP,
Not for motor type: -
VECTOR_G, B_INF,
TM31, TM120, TM150,
Min
TB30, ENC
-
Description:
Displays the saved BO/CO parameters (signal source), which are located on drive objects that are either not capable
of operation or have been deactivated.
Dependency:
Refer to: p9495, p9496, p9497, p9498
Refer to: A01318, A01507
Note:
A BICO interconnection (signal sink, signal source) is displayed in the same index of p9498 and p9499.
p9500
SI Motion monitoring clock cycle (Control Unit) / SI Mtn clock CU
VECTOR_G
Can be changed: C2(95)
Data type: FloatingPoint32
P-Group: Safety Integrated
Not for motor type: -
Min
0.50000 [ms]
Description:
Sets the monitoring clock cycle for safe motion monitoring.
Dependency:
Refer to: r2064, p9511
Refer to: F01652
Note:
A change only becomes effective after a POWER ON.
The monitoring clock cycle must be a multiple of the actual value sensing clock cycle (see the parameter description
for p9511).
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
25.00000 [ms]
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
12.00000 [ms]
927

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

SinamicsG150

Table of Contents