2 Parameters
2.2 List of parameters
Note:
A factory setting run can only be started if p0010 was first set to 30 (parameter reset).
At the end of the calculations, p0970 is automatically set to 0.
Parameter reset has been completed if p0970 and p0010 have been set to 0.
For p0970 = 5 the following applies:
The password for Safety Integrated must be set.
When Safety Integrated is enabled, this can result in error messages, which then require an acceptance test to be
performed.
Then save the parameters and carry out a POWER ON.
p0970
Reset drive parameters / Drive par reset
VECTOR_G
Can be changed: C2(30)
Data type: Unsigned16
P-Group: Factory settings
Not for motor type: -
Min
0
Description:
The parameter is used to initiate the reset of the parameters of an individual drive unit.
Parameters p0100, p0205 (only for VECTOR) and the parameters of the basic drive commissioning (p0009) are not
reset (p0107, p0108, p0111, p0112, p0115, p0121, p0130, p0131, p0140, p0141, p0142, p0170, p0186 ... p0189).
These can only be reset using the factory setting of the complete drive unit (p0976).
Value:
0:
1:
5:
6:
100:
Dependency:
Refer to: F01659
Notice:
After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
Note:
A factory setting run can only be started if p0010 was first set to 30 (parameter reset).
At the end of the calculations, p0970 is automatically set to 0.
Parameter reset has been completed if p0970 and p0010 have been set to 0.
For p0970 = 5 the following applies:
The password for Safety Integrated must be set.
When Safety Integrated is enabled, this can result in error messages, which then require an acceptance test to be
performed.
Then save the parameters and carry out a POWER ON.
For p0970 = 1 the following applies:
If a Safety Integrated function is parameterized (p9601), then the safety parameters are not reset. In this case, a fault
F01659 is output with fault value 2.
p0970
Reset infeed parameter / INF par reset
B_INF
Can be changed: C2(30)
Data type: Unsigned16
P-Group: Factory settings
Not for motor type: -
Min
0
Description:
The parameter is used to initiate a reset of the parameters of an individual infeed unit.
The parameters of the basic commissioning (refer to p0009) are in this case not reset (p0107, p0108, p0121, p0170).
These can only be reset using the factory setting of the complete drive unit (p0976).
The sampling times (p0111, p0112, p0115) are only not reset if this results in a conflict with the basic clock cycle
(p0110).
Value:
0:
1:
100:
296
Inactive
Start a parameter reset
Starts a safety parameter reset
Start reset non-safety/safety parameters
Start a BICO interconnection reset
Inactive
Start a parameter reset
Start a BICO interconnection reset
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
100
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
100
List Manual (LH2), 07/2016, A5E03263479A
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
SINAMICS G130/G150

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

SinamicsG150

Table of Contents