p4080[0...1]
TM31 analog outputs characteristic value y2 / TM31 AO char y2
TM31
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Terminals
Not for motor type: -
Min
-20.000 [V]
Description:
Sets the scaling characteristic for the analog outputs of Terminal Module 31 (TM31).
The scaling characteristic for the analog outputs is defined using 2 points.
This parameter specifies the y coordinate (output voltage in V or output current in mA) of the 2nd value pair of the
characteristic.
Index:
[0] = AO 0 (X522.1, X522.2, X522.3)
[1] = AO 1 (X522.4, X522.5, X522.6)
Dependency:
The unit of this parameter (V or mA) depends on the analog output type.
Refer to: r4076, p4076
Notice:
This parameter is automatically overwritten when changing p4076 (type of analog outputs).
Note:
The parameters for the characteristic do not have a limiting effect.
p4080[0...1]
TB30 analog outputs characteristic value y2 / TB30 AO char y2
TB30
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Terminals
Not for motor type: -
Min
-11.000 [V]
Description:
Sets the scaling characteristic for the analog outputs of Terminal Board 30 (TB30).
The scaling characteristic for the analog outputs is defined using 2 points.
This parameter specifies the y coordinate (output voltage in V) of the 2nd value pair of the characteristic.
Index:
[0] = AO 0 (X482.5/X482.6)
[1] = AO 1 (X482.7/X482.8)
Note:
The parameters for the characteristic do not have a limiting effect.
p4082[0...1]
BI: TM31 analog outputs invert signal source / TM31 AO inv s_src
TM31
Can be changed: U, T
Data type: Unsigned32 / Binary
P-Group: Terminals
Not for motor type: -
Min
-
Description:
Sets the signal source to invert the analog output signals of Terminal Module 31 (TM31).
Index:
[0] = AO 0 (X522.1, X522.2, X522.3)
[1] = AO 1 (X522.4, X522.5, X522.6)
p4082[0...1]
BI: TB30 analog outputs invert signal source / TB30 AO inv s_src
TB30
Can be changed: U, T
Data type: Unsigned32 / Binary
P-Group: Terminals
Not for motor type: -
Min
-
Description:
Sets the signal source for inverting the analog output signals of the Terminal Board 30 (TB30).
Index:
[0] = AO 0 (X482.5/X482.6)
[1] = AO 1 (X482.7/X482.8)
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
20.000 [V]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
11.000 [V]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: 9572
Unit selection: -
Expert list: 1
Factory setting
10.000 [V]
Access level: 2
Func. diagram: 9106
Unit selection: -
Expert list: 1
Factory setting
10.000 [V]
Access level: 3
Func. diagram: 9572
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 9106
Unit selection: -
Expert list: 1
Factory setting
0