p7857
Sub-boot mode / Sub-boot mode
VECTOR_G, B_INF,
Can be changed: U, T
TM31, TM120, TM150,
Data type: Integer16
TB30, TM54F_MA,
P-Group: -
TM54F_SL, ENC, HUB
Not for motor type: -
Min
0
Description:
Sets the mode for the sub-boot.
Value:
0:
1:
Note:
For p7857 = 0 (manual sub-boot) the following applies:
The parameter should be set to 1 to start the sub-boot.
p7859[0...199]
Component number global / Comp_no global
CU_G130_PN,
Can be changed: U, T
CU_G150_PN,
Data type: Integer16
CU_G130_DP,
P-Group: -
CU_G150_DP
Not for motor type: -
Min
-32786
Description:
Sets the global and unique component number in a drive system with several Control Units.
Each index of the parameter corresponds to a possible local component number on the corresponding Control Unit.
The indices are allocated to the global component numbers as follows:
p7859[0]: Not used
p7859[1]: Sets the global component number for the local component number 1
p7859[2]: Sets the global component number for the local component number 2
...
p7859[199]: Sets the global component number for the local component number 199
Notice:
This parameter is preferably set via suitable commissioning software (e.g. UpdateAgent, STARTER, SCOUT).
Changing the parameter via the AOP (Advanced Operator Panel) or BOP (Basic Operator Panel) can destroy a valid
unique setting.
Note:
The parameter is not influenced by setting the factory setting.
r7867
Status/configuration changes global / Changes global
CU_G130_PN,
Can be changed: -
CU_G150_PN,
Data type: Unsigned32
CU_G130_DP,
P-Group: -
CU_G150_DP
Not for motor type: -
Min
-
Description:
Displays status and configuration changes of all of the drive objects in the complete unit.
When changing the status or the configuration of the Control Unit or a drive object, the value of this parameter is
incremented.
Dependency:
Refer to: r7868, r7869, r7870
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Sub-boot manual
Sub-boot automatic
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
1
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
32767
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
2 Parameters
2.2 List of parameters
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 0
Factory setting
0
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
789