r1298
CO: Vdc controller output (U/f) / Vdc_ctrl output
VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Functions
Not for motor type: -
Min
- [rpm]
Description:
Displays the actual output of the Vdc controller (DC link voltage controller)
p1300[0...n]
Open-loop/closed-loop control operating mode / Op/cl-lp ctrl_mode
VECTOR_G
Can be changed: C2(1), T
Data type: Integer16
P-Group: V/f open-loop control
Not for motor type: -
Min
0
Description:
Sets the U/f control mode of the drive.
Value:
0:
1:
2:
3:
4:
5:
6:
7:
15:
19:
Recommendation:
The use of the vector control operating modes is recommended for synchronous motors.
Dependency:
If you are working with reduced supply voltages (p0212.0 = 1), only U/f control with independent voltage setpoint
(p1300 = 19) can be set as the operating mode.
p1300 = 15 (operation with braking resistor), can only be activated or deactivated in quick commissioning (p0010 =
1). This operating mode is only possible for chassis power units (DC/AC Motor Module).
Notice:
Active slip compensation is required in the U/f control types with Eco mode (p1300 = 4, 7). The scaling of the slip
compensation (p1335) should be set so that the slip is completely compensated (generally 100%).
The Eco mode is only effective in steady-state operation and when the ramp-function generator is not bypassed. In
the case of analog setpoints, if required the tolerance for ramp-up and ramp-down should be actively increased for
the ramp-function generator using p1148 in order to reliably signal a steady-state condition.
Note:
The closed-loop torque control can only be changed over in operation (p1300 = 20, 21) by selecting the closed-loop
speed control (p1501). At the changeover, the setting of p1300 does not change. In this case, the actual state is
displayed in r1407, bit 2 and bit 3.
For motors, type p0300 = 14, operation with U/f control is only recommended for diagnostic purposes.
p1300[0...n]
Open-loop/closed-loop control operating mode / Op/cl-lp ctrl_mode
VECTOR_G (n/M)
Can be changed: C2(1), T
Data type: Integer16
P-Group: V/f open-loop control
Not for motor type: -
Min
0
Description:
Sets the open and closed-loop control mode of a drive.
Value:
0:
1:
2:
3:
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
U/f control with linear characteristic
U/f control with linear characteristic and FCC
U/f control with parabolic characteristic
U/f control with parameterizable characteristic
U/f control with linear characteristic and ECO
U/f control for drives requiring a precise freq. (e.g. textiles)
U/f control for drives requiring a precise frequency and FCC
U/f control for a parabolic characteristic and ECO
Operation with braking resistor
U/f control with independent voltage setpoint
U/f control with linear characteristic
U/f control with linear characteristic and FCC
U/f control with parabolic characteristic
U/f control with parameterizable characteristic
Calculated: -
Dyn. index: -
Unit group: 3_1
Scaling: p2000
Max
- [rpm]
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
19
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
23
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 6320
Unit selection: p0505
Expert list: 1
Factory setting
- [rpm]
Access level: 2
Func. diagram: 6300, 6301,
8012
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 6300, 6301,
8012
Unit selection: -
Expert list: 1
Factory setting
20
371