Siemens G130 List Manual page 502

Hide thumbs Also See for G130:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
Note:
For controller STOP, the additional monitoring time is not effective.
p2048
IF1 PROFIdrive PZD sampling time / IF1 PZD t_sample
CU_G130_PN,
Can be changed: C1(3)
CU_G150_PN,
Data type: FloatingPoint32
CU_G130_DP,
P-Group: Communications
CU_G150_DP
Not for motor type: -
Min
1.00 [ms]
Description:
Sets the sampling time for the cyclic interface 1 (IF1).
Note:
The system only permits certain sampling times and after writing to this parameter, displays the value that has
actually been set.
For clock cycle synchronous operation, the specified bus cycle time applies (Tdp).
r2050[0...19]
CO: IF1 PROFIdrive PZD receive word / IF1 PZD recv word
CU_G130_PN,
Can be changed: -
CU_G150_PN,
Data type: Integer16
CU_G130_DP,
P-Group: Communications
CU_G150_DP
Not for motor type: -
Min
-
Description:
Connector output to interconnect PZD (setpoints) with word format received from the fieldbus controller.
Index:
[0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
[4] = PZD 5
[5] = PZD 6
[6] = PZD 7
[7] = PZD 8
[8] = PZD 9
[9] = PZD 10
[10] = PZD 11
[11] = PZD 12
[12] = PZD 13
[13] = PZD 14
[14] = PZD 15
[15] = PZD 16
[16] = PZD 17
[17] = PZD 18
[18] = PZD 19
[19] = PZD 20
Note:
IF1: Interface 1
r2050[0...31]
CO: IF1 PROFIdrive PZD receive word / IF1 PZD recv word
VECTOR_G
Can be changed: -
Data type: Integer16
P-Group: Communications
Not for motor type: -
Min
-
Description:
Connector output to interconnect PZD (setpoints) with word format received from the fieldbus controller.
Index:
[0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
[4] = PZD 5
[5] = PZD 6
502
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
16.00 [ms]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: 4000H
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: 4000H
Max
-
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
4.00 [ms]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: 2440, 2468
Unit selection: -
Expert list: 1
Factory setting
-
SINAMICS G130/G150

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

SinamicsG150

Table of Contents