Siemens G130 List Manual page 501

Hide thumbs Also See for G130:
Table of Contents

Advertisement

r2043.0...2
BO: IF1 PROFIdrive PZD state / IF1 PD PZD state
CU_G130_PN,
Can be changed: -
CU_G150_PN,
Data type: Unsigned8
CU_G130_DP,
P-Group: Communications
CU_G150_DP
Not for motor type: -
Min
-
Description:
Displays the PROFIdrive PZD state.
Bit field:
Bit
00
01
02
Dependency:
Refer to: p2044
Note:
When using the "setpoint failure" signal, the bus can be monitored and an application-specific response triggered
when the setpoint fails.
p2044
IF1 PROFIdrive fault delay / IF1 PD fault delay
VECTOR_G, B_INF,
Can be changed: U, T
ENC
Data type: FloatingPoint32
P-Group: Communications
Not for motor type: -
Min
0 [s]
Description:
Sets the delay time to initiate fault F01910 after a setpoint failure.
The time until the fault is initiated can be used by the application. This means that is is possible to respond to the
failure while the drive is still operational (e.g. emergency retraction).
Dependency:
Refer to: r2043
p2045
CI: PB/PN clock synchronous controller sign-of-life signal source /
PB/PN ctrSoL s_src
VECTOR_G (n/M),
Can be changed: T
ENC
Data type: Unsigned32 / Integer16
P-Group: Communications
Not for motor type: -
Min
-
Description:
Connector input for the sign-of-life of the clock synchronous PROFIBUS/PROFINET controller.
The sign-of-life is expected at bits 12 to 15. Bits 0 to 11 are not evaluated.
The sign-of-life signal is normally received in PZD4 (control word 2) from the controller.
Dependency:
Refer to: p0925, r2065
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p2047
PROFIBUS additional monitoring time / PB suppl t_monit
CU_G130_DP,
Can be changed: U, T
CU_G150_DP
Data type: FloatingPoint32
P-Group: Communications
Not for motor type: -
Min
0 [ms]
Description:
Sets the additional monitoring time to monitor the process data received via PROFIBUS.
Enables short bus faults to be compensated.
If no process data is received within this time, then an appropriate message is output.
Recommendation:
In the isochronous mode, the additional monitoring time should not be set.
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Signal name
Setpoint failure
Clock cycle synchronous operation active
Fieldbus oper
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
1 signal
Yes
Yes
Yes
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
100 [s]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
20000 [ms]
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 2410
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
No
No
No
Access level: 3
Func. diagram: 2410
Unit selection: -
Expert list: 1
Factory setting
0 [s]
Access level: 3
Func. diagram: 2410
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 2410
Unit selection: -
Expert list: 1
Factory setting
0 [ms]
FP
-
-
-
501