2 Parameters
2.2 List of parameters
Regarding the state "active" (r1238 = 2), "active - feedback signal "Closed" OK" (r1238 = 3)", "active - feedback
signal "Closed" missing" (r1238 = 4)":
- the control signal to close contactor r1239.0 is set to "1" (closed) and the pulses are suppressed.
- if a contactor feedback signal is not connected (BI: p1235 = 0 signal), then a transition is immediately made into
state 3.
- if a contactor feedback signal is connected, then a transition is made into state 3 if the feedback signal at BI: p1235
goes to "1" (closed) within the monitoring time (p1236).
- otherwise, a transition is made into state 4.
For state "prompt to remove the armature short-circuit" (r1238 = 5):
- the activation criterion is no longer fulfilled. An attempt is made to again remove the armature short circuit.
- the control signal to close the contactor r1239.0 is set to "0" (open) and the pulses remain suppressed.
- if a contactor feedback signal is not connected (BI: p1235 = 0 signal), the system waits for the delay time (p1237) to
expire until a transition is made into state 1.
- if a contactor feedback signal is connected, the system waits until the feedback signal at BI:p1235 goes to "0"
(open) until a transition is made into state 1. If this does not occur within the monitoring time (p1236), then a transition
is made into state 6.
For state "active - feedback signal "Open" missing" (r1238 = 6):
- this error state can be exited by de-selecting the external armature short-circuit (p1231 = 0).
r1239.0...13
CO/BO: Armature short-circuit / DC braking status word / ASC/DCBRK ZSW
VECTOR_G
Can be changed: -
Data type: Unsigned32
P-Group: Functions
Not for motor type: -
Min
-
Description:
Displays the status word for armature short-circuit.
Bit field:
Bit
00
01
02
03
04
05
06
08
09
10
11
12
13
Dependency:
Refer to: p1230, p1231, p1232, p1233, p1234, p1235, p1236, p1237
Note:
External armature short-circuit (bits 0 ... 3):
For bit 00:
Using this signal, the motor is short-circuited through an external contactor circuit. This means that this BO: p1239.0
must be interconnected e.g. to a digital output.
For bit 01:
This signal indicates the state of the contactor to establish the armature short-circuit. To do this, BI: p1235 must be
interconnected to a digital input.
For bit 02:
The external armature short-circuit configuration is ready and is activated as soon as the activation criterion is
fulfilled.
For bit 03:
1: A feedback signal from an external contactor was parameterized in BI: p1235.
Internal voltage protection / internal armature short-circuit (bits 4 ... 6):
354
Signal name
External armature short-circuit
External armature short-circuit contactor
feedback signal
External armature short-circuit ready
External armature short-circuit with
contactor feedback signal
Internal armature short-circuit
Internal armature short circuit feedback
signal from power unit
Internal armature short-circuit ready
DC braking active
DC current injection active
DC braking ready
Armature short circuit/DC braking selected
DC braking selection internally inhibited
DC braking for OFF1/OFF3
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
1 signal
Active
Closed
Yes
Yes
Active
Active
Yes
Yes
Yes
Yes
Yes
Yes
Yes
List Manual (LH2), 07/2016, A5E03263479A
Access level: 1
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
Inactive
Open
No
No
Inactive
Inactive
No
No
No
No
No
No
No
SINAMICS G130/G150
FP
-
-
-
-
-
-
-
7017
-
7017
-
-
-