Siemens G130 List Manual page 234

Hide thumbs Also See for G130:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
The following applies from firmware version 4.7 SP6 and p0612.8 = 1:
- p5390: when commissioning a catalog motor for the first time, p0605 is copied to p5390.
- p5390: p5390 is of significance when evaluating the alarm threshold.
- p5390: the stator winding temperature (r0632) is used to initiate the signal.
- p0627: when a catalog motor is commissioned for the first time, p0605 -40 °C is copied to p0627.
- p0627: p0627 is of significance for the rated temperature.
Motor temperature model 2 (p0612.1 = 1) or measurement:
- sets the fault threshold. If the temperature (r0035) exceeds the fault threshold, then fault F07011 is output.
Dependency:
Refer to: r0034, p0606, p0611, p0612
Refer to: F07011, A07012
Notice:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Motor temperature model 1 (I2t):
The following applies for firmware version < 4.7 SP6 or p0612.8 = 0:
p0605 also defines the final temperature of the model for r0034 = 100 %. Therefore, p0605 has no influence on the
time up to alarm A07012 being issued. The time is only determined by time constant p0611, the actual current and
the reference value p0318. For p0318 = 0, the rated motor current is used as reference value.
Note:
The hysteresis is 2 K.
When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (p0300).
p0606[0...n]
Mot_temp_mod 2: sensor timer / Mod 2:sens timer
VECTOR_G
Can be changed: C2(3), U, T
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: -
Min
0.000 [s]
Description:
Sets the timer for monitoring the motor temperature for motor temperature model 2 or KTY/PT1000.
This timer is started when the temperature alarm threshold (p0604) is exceeded.
If the timer has expired and the alarm threshold has, in the meantime, not been fallen below, then fault F07011 is
output.
If the temperature fault threshold (p0605) is prematurely exceeded before the timer has expired, then fault F07011 is
immediately output.
Dependency:
Refer to: p0604, p0605
Refer to: F07011, A07910
Note:
With p0606 = 0 s, the timer is deactivated and only the fault threshold is effective.
KTY/PT1000: When setting the minimum value, the timer is disabled and a fault is not output until p0605 is
exceeded.
PTC, bimetallic NC contact: The timer minimum value has no special significance.
p0607[0...n]
Temperature sensor fault timer / Sensor fault time
VECTOR_G
Can be changed: C2(3), U, T
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: -
Min
0.000 [s]
Description:
Sets the timer between the output of alarm and fault for a temperature sensor fault.
If there is a sensor fault, this timer is started.
If the sensor fault is still present after the timer has expired, a corresponding fault is output.
Notice:
The parameterized time is internally rounded-off to an integer multiple of 48 ms.
Note:
If the motor is an induction motor, the timer is switched off when setting the minimum value and no alarm is output.
Temperature monitoring is then based on the thermal model.
234
Calculated: -
Dyn. index: MDS, p0130
Unit group: -
Scaling: -
Max
600.000 [s]
Calculated: -
Dyn. index: MDS, p0130
Unit group: -
Scaling: -
Max
600.000 [s]
List Manual (LH2), 07/2016, A5E03263479A
Access level: 2
Func. diagram: 8016
Unit selection: -
Expert list: 1
Factory setting
0.000 [s]
Access level: 2
Func. diagram: 8016
Unit selection: -
Expert list: 1
Factory setting
0.100 [s]
SINAMICS G130/G150

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

SinamicsG150

Table of Contents