p3811[0...n]
Sync-line-drive frequency limiting / Sync f_lim
VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Functions
Not for motor type: -
Min
0.00 [Hz]
Description:
Sets the frequency limiting of the phase controller output for the line-drive synchronization.
r3812
CO: Sync-line-drive correction frequency / Sync f_corr
VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Functions
Not for motor type: -
Min
- [Hz]
Description:
Displays the correction frequency for the line-drive synchronization.
p3813[0...n]
Sync-line-drive phase synchronism threshold value / Sync Ph_sync thrsh
VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Functions
Not for motor type: -
Min
1.00 [°]
Description:
Sets the threshold value of the phase synchronism for the line-drive synchronization.
A prerequisite for synchronism is achieved if the phase difference is lower than the threshold value.
Note:
Synchronism is reached (r3819.2 = 1), if the AND logic operation of the results from the phase measurement (p3813)
and voltage measurement (p3815) is fulfilled.
r3814
CO: Sync-line-drive voltage difference / Sync U_diff
VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Functions
Not for motor type: -
Min
- [Vrms]
Description:
Display and connector output for the voltage difference between the measured target voltage and output voltage of
the gating unit of the closed-loop control for line-drive synchronization.
p3815[0...n]
Sync-line-drive voltage difference threshold value / Sync U_diff thresh
VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Functions
Not for motor type: -
Min
0.00 [%]
Description:
Sets the threshold value of the voltage difference for the line-drive synchronization.
A prerequisite for synchronism is reached if the voltage difference is less than the threshold value.
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
1.00 [Hz]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: p2000
Max
- [Hz]
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
20.00 [°]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: p2001
Max
- [Vrms]
Calculated:
CALC_MOD_LIM_REF
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
20.00 [%]
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: 7020
Unit selection: -
Expert list: 1
Factory setting
0.20 [Hz]
Access level: 2
Func. diagram: 3080, 7020
Unit selection: -
Expert list: 1
Factory setting
- [Hz]
Access level: 2
Func. diagram: 7020
Unit selection: -
Expert list: 1
Factory setting
2.00 [°]
Access level: 2
Func. diagram: 7020
Unit selection: -
Expert list: 1
Factory setting
- [Vrms]
Access level: 2
Func. diagram: 7020
Unit selection: -
Expert list: 1
Factory setting
10.00 [%]