Siemens G130 List Manual page 651

Hide thumbs Also See for G130:
Table of Contents

Advertisement

p4058[0...1]
TB30 analog inputs characteristic value y1 / TB30 AI char y1
TB30
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Terminals
Not for motor type: -
Min
-1000.00 [%]
Description:
Sets the scaling characteristic for the analog inputs of Terminal Board 30 (TB30).
The scaling characteristic for the analog inputs is defined using 2 points.
This parameter specifies the y coordinate (percentage) of the 1st value pair of the characteristic.
Index:
[0] = AI 0 (X482.1/X482.2)
[1] = AI 1 (X482.3/X482.4)
Note:
The parameters for the characteristic do not have a limiting effect.
p4059[0...1]
TM31 analog inputs characteristic value x2 / TM31 AI char x2
TM31
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Terminals
Not for motor type: -
Min
-20.000
Description:
Sets the scaling characteristic for the analog inputs of Terminal Module 31 (TM31).
The scaling characteristic for the analog inputs is defined using 2 points.
This parameter specifies the x coordinate (input voltage in V or input current in mA) of the 2nd value pair of the
characteristic.
Index:
[0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Dependency:
The unit of this parameter (V or mA) depends on the analog input type.
Refer to: r4056, p4056
Notice:
This parameter is automatically overwritten when the analog input type (p4056) is modified.
Note:
The parameters for the characteristic do not have a limiting effect.
p4059[0...1]
TB30 analog inputs characteristic value x2 / TB30 AI char x2
TB30
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Terminals
Not for motor type: -
Min
-11.000 [V]
Description:
Sets the scaling characteristic for the analog inputs of Terminal Board 30 (TB30).
The scaling characteristic for the analog inputs is defined using 2 points.
This parameter specifies the x coordinate (input voltage in V) of the 2nd value pair of the characteristic.
Index:
[0] = AI 0 (X482.1/X482.2)
[1] = AI 1 (X482.3/X482.4)
Note:
The parameters for the characteristic do not have a limiting effect.
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
1000.00 [%]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
20.000
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
11.000 [V]
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: 9104
Unit selection: -
Expert list: 1
Factory setting
0.00 [%]
Access level: 2
Func. diagram: 9566, 9568
Unit selection: -
Expert list: 1
Factory setting
10.000
Access level: 2
Func. diagram: 9104
Unit selection: -
Expert list: 1
Factory setting
10.000 [V]
651

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

SinamicsG150

Table of Contents