Siemens G130 List Manual page 907

Hide thumbs Also See for G130:
Table of Contents

Advertisement

p9344
SI Motion actual value comparison tolerance (referencing) (MM) / SI mtn ref tol MM
VECTOR_G (Safety
Can be changed: C2(95)
rot)
Data type: FloatingPoint32
P-Group: Safety Integrated
Not for motor type: -
Min
0.0000 [°]
Description:
Sets the tolerance for checking the actual values.
For an incremental encoder, the actual values are checked after referencing; for an absolute encoder, when
switching on.
Dependency:
Refer to: C01711
Notice:
This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note:
A change only becomes effective after a POWER ON.
For linear axes, the maximum value is limited to 1 mm.
p9345
SI Motion SSM filter time (Motor Module) / SI Mtn SSM filt MM
VECTOR_G
Can be changed: C2(95)
Data type: FloatingPoint32
P-Group: Safety Integrated
Not for motor type: -
Min
0.00 [µs]
Description:
Sets the filter time for the SSM feedback signal to detect standstill (n < nx).
Notice:
This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note:
The filter time is effective only if the function is enabled (p9301.16 = p9501.16 = 1).
The set time is rounded internally to an integer multiple of the monitoring clock cycle.
The parameter is included in the crosswise data comparison of the two monitoring channels.
SSM: Safe Speed Monitor (safety-relevant feedback signal from the velocity monitoring)
p9346
SI Motion SSM velocity limit (Motor Module) / SI Mtn SSM v_limMM
VECTOR_G
Can be changed: C2(95)
Data type: FloatingPoint32
P-Group: Safety Integrated
Not for motor type: -
Min
0.00 [mm/min]
Description:
Sets the velocity limit for the SSM feedback signal to detect standstill (n < nx).
When this limit value is undershot, the signal "SSM feedback signal active" is set.
For p9368 = p9568 = 0, the value in p9346/p9546 is also applicable for SAM/SBR.
Dependency:
Refer to: p9546
Caution:
The "SAM/SBR" function is deactivated if the selected threshold value is undershot.
Notice:
This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note:
SAM: Safe Acceleration Monitor (safe acceleration monitoring)
SBR: Safe Brake Ramp (safe brake ramp monitoring)
SSM: Safe Speed Monitor (safety-relevant feedback signal from the velocity monitoring)
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
36.0000 [°]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
500000.00 [µs]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
1000000.00 [mm/min]
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0.0100 [°]
Access level: 3
Func. diagram: 2823
Unit selection: -
Expert list: 1
Factory setting
0.00 [µs]
Access level: 3
Func. diagram: 2823
Unit selection: -
Expert list: 1
Factory setting
20.00 [mm/min]
907

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

SinamicsG150

Table of Contents