Siemens G130 List Manual page 1055

Hide thumbs Also See for G130:
Table of Contents

Advertisement

p10046
SI TM54F F-DO feedback signal input activation / SI F-DO FS act
TM54F_MA,
Can be changed: C2(95)
TM54F_SL
Data type: Unsigned32
P-Group: Safety Integrated
Not for motor type: -
Min
-
Description:
Activates the readback input for the safety digital outputs (F-DO)
The test mode for the particular safety digital output is set in p10047.
Bit field:
Bit
00
01
02
03
Dependency:
Refer to: p10047
Note:
F-DO: Failsafe Digital Output
p10047[0...3]
SI TM54F F-DO test stop mode / SI F-DO test mode
TM54F_MA,
Can be changed: C2(95)
TM54F_SL
Data type: Integer16
P-Group: Safety Integrated
Not for motor type: -
Min
1
Description:
Sets the test stop mode for the particular safety digital output (F-DO)
Index 0: F-DO 0
Index 1: F-DO 1
Index 2: F-DO 2
Index 3: F-DO 3
Value:
1:
2:
3:
Note:
If value = 1:
When this test mode is being used, and excessive resistance of the load between DO+ and DO- can lead to
problems during the test stop. It is therefore important to make sure that the load resistance at an individual F-DO
does not exceed 10 kOhm.
p10048
SI TM54F F-DI F-DO test stop configuration / SI teststop config
TM54F_MA
Can be changed: C2(95)
Data type: Integer16
P-Group: Safety Integrated
Not for motor type: -
Min
0
Description:
Configures the test stop for F-DI and F-DO of the TM54F.
If the automatic test stop is activated, then the test stop can still be started using binector input p10007.
Note:
The automatic test stop is started after power up, partial power up or a warm restart.
Value:
0:
1:
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Signal name
Read back F-DO 0
Read back F-DO 1
Read back F-DO 2
Read back F-DO 3
Test mode 1 evaluation of int. diagnostic signal (passive load)
Test mode 2 read back F-DO in DI (relay circuit)
Test mode 3 read back F-DO in DI (actuator with feedback signal)
Manual test stop via BICO p10007
Automatic test stop
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
1 signal
Test active
Test active
Test active
Test active
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
3
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
1
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 2892
Unit selection: -
Expert list: 1
Factory setting
0000 bin
0 signal
No test
No test
No test
No test
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
2
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
FP
-
-
-
-
1055