p0608[0...3]
CI: Motor temperature signal source 2 / Mot_temp S_src 2
VECTOR_G
Can be changed: C2(3), T
Data type: Unsigned32 / FloatingPoint32
P-Group: Motor
Not for motor type: -
Min
-
Description:
Sets signal source 2 to evaluate the motor temperature via a BICO interconnection.
Index:
[0] = Motor temperature channel 1
[1] = Motor temperature channel 2
[2] = Motor temperature channel 3
[3] = Motor temperature channel 4
Dependency:
Refer to: p0600
Note:
Temperature sensor KTY/PT1000:
Valid temperature range -48 °C ... 248 °C.
Temperature sensor PTC/bimetal:
For a value of -50 °C, the following applies: Motor temperature < nominal response temperature of the PTC (bimetal
contact closed).
For a value of 250 °C, the following applies: Motor temperature >= nominal response temperature of the PTC
(bimetal contact open).
Note:
When using a Terminal Module 120 (TM120), the following applies:
- the sensor type used is set using p4100.
- the temperature signal is interconnected using connector output r4105.
p0609[0...3]
CI: Motor temperature signal source 3 / Mot_temp S_src 3
VECTOR_G
Can be changed: C2(3), T
Data type: Unsigned32 / FloatingPoint32
P-Group: Motor
Not for motor type: -
Min
-
Description:
Sets signal source 3 to evaluate the motor temperature via a BICO interconnection.
Index:
[0] = Motor temperature channel 1
[1] = Motor temperature channel 2
[2] = Motor temperature channel 3
[3] = Motor temperature channel 4
Dependency:
Refer to: p0600
Note:
Temperature sensor KTY/PT1000:
Valid temperature range -48 °C ... 248 °C.
Temperature sensor PTC/bimetal:
For a value of -50 °C, the following applies: Motor temperature < nominal response temperature of the PTC (bimetal
contact closed).
For a value of 250 °C, the following applies: Motor temperature >= nominal response temperature of the PTC
(bimetal contact open).
Note:
When using a Terminal Module 120 (TM120), the following applies:
- the sensor type used is set using p4100.
- the temperature signal is interconnected using connector output r4105.
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Calculated: -
Dyn. index: -
Unit group: -
Scaling: p2006
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: p2006
Max
-
2 Parameters
2.2 List of parameters
Access level: 2
Func. diagram: 8016
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 8016
Unit selection: -
Expert list: 1
Factory setting
0