2 Parameters
2.2 List of parameters
r7240[0...n]
Par_circuit gating unit status word 1 / Gating unit ZSW1
VECTOR_G (Parallel) Can be changed: -
Data type: Unsigned16
P-Group: Displays, signals
Not for motor type: -
Min
-
Description:
Displays status word 1 of the power unit.
Bit field:
Bit
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
r7250[0...4]
Par_circuit power unit rated power / PU P_rated
VECTOR_G (Parallel),
Can be changed: -
B_INF (Parallel)
Data type: FloatingPoint32
P-Group: Converter
Not for motor type: -
Min
- [kW]
Description:
Displays the rated power of the individual power units connected in parallel for various load duty cycles.
The sum of the rated powers of all power units connected in parallel is displayed in r0206.
Index:
[0] = Rated value
[1] = Load duty cycle with low overload
[2] = Load duty cycle with high overload
[3] = S1 cont duty cyc
[4] = S6 load duty cycle
Dependency:
The value is displayed in [kW] or [hp].
Refer to: p0100, p0205
r7251[0...4]
Par_circuit power unit rated current / PU PI_rated
VECTOR_G (Parallel),
Can be changed: -
B_INF (Parallel)
Data type: FloatingPoint32
P-Group: Converter
Not for motor type: -
Min
- [Arms]
Description:
Displays the rated current of the individual power units connected in parallel for various load duty cycles.
The sum of the rated currents of all power units connected in parallel is displayed in r0207.
Index:
[0] = Rated value
[1] = Load duty cycle with low overload
[2] = Load duty cycle with high overload
766
Signal name
Fault time-critical
Gating unit mode bit 0
Pulse enable
Upper switch-off signal path
Lower switch-off signal path
Gating unit mode bit 1
Gating unit mode bit 2
Brake state
Brake diagnostics
Armature short-circuit braking
Gating unit state bit 0
Gating unit state bit 1
Gating unit state bit 2
Alarm status bit 0
Alarm status bit 1
Diagnostics 24 V
Calculated: -
Dyn. index: PDS, p0120
Unit group: -
Scaling: -
Max
-
1 signal
ON
ON
ON
Inactive
Inactive
ON
ON
ON
ON
Active
ON
ON
ON
ON
ON
ON
Calculated: -
Dyn. index: -
Unit group: 14_6
Scaling: -
Max
- [kW]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
- [Arms]
List Manual (LH2), 07/2016, A5E03263479A
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
OFF
OFF
OFF
Active
Active
OFF
OFF
OFF
OFF
Not active
OFF
OFF
OFF
OFF
OFF
OFF
Access level: 2
Func. diagram: -
Unit selection: p0100
Expert list: 1
Factory setting
- [kW]
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
- [Arms]
SINAMICS G130/G150