2 Parameters
2.2 List of parameters
p0806
BI: Inhibit master control / PcCtrl inhibit
VECTOR_G, B_INF
Can be changed: T
Data type: Unsigned32 / Binary
P-Group: Commands
Not for motor type: -
Min
-
Description:
Sets the signal source to block the master control.
Dependency:
Refer to: r0807
Note:
The commissioning software (drive control panel) uses the master control, for example.
r0807.0
BO: Master control active / PcCtrl active
VECTOR_G, B_INF
Can be changed: -
Data type: Unsigned8
P-Group: Displays, signals
Not for motor type: -
Min
-
Description:
Displays what has the master control.
The drive can be controlled via the BICO interconnection or from external (e.g. the commissioning software).
Bit field:
Bit
00
Dependency:
Refer to: p0806
Notice:
The master control only influences control word 1 and speed setpoint 1. Other control word/setpoints can be
transferred from another automation device.
Note:
Bit 0 = 0: BICO interconnection active
Bit 0 = 1: Master control for PC/AOP
The commissioning software (drive control panel) uses the master control, for example.
p0809[0...2]
Copy Command Data Set CDS / Copy CDS
VECTOR_G
Can be changed: T
Data type: Unsigned8
P-Group: Commands
Not for motor type: -
Min
0
Description:
Copies one Command Data Set (CDS) into another.
Index:
[0] = Source Command Data Set
[1] = Target Command Data Set
[2] = Start copying procedure
Note:
Procedure:
1. In Index 0, enter which command data set should be copied.
2. In index 1, enter the command data set that is to be copied into.
3. Start copying: set index 2 from 0 to 1.
p0809[2] is automatically set to 0 when copying is completed.
266
Signal name
Master control active
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
1 signal
Yes
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
15
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
No
Access level: 2
Func. diagram: 8560
Unit selection: -
Expert list: 1
Factory setting
0