4:
5:
6:
7:
8:
Dependency:
Refer to: p7003
Notice:
The parameter is only evaluated if p7003 = 2.
Note:
For p6397 = 0 the following applies: The second systems leads for a positive direction of rotation.
For p6397 = 1 the following applies: The second systems lags for a positive direction of rotation.
p6700[0...n]
Voltage model angle smoothing / U_mod ang smooth
VECTOR_G (n/M)
Can be changed: U, T
Data type: FloatingPoint32
P-Group: -
Not for motor type: ASM, PMSM, REL
Min
0 [ms]
Description:
Sets the smoothing of the flux orientation of the voltage model for a separately excited synchronous motor.
p6870[0...n]
VSM offset voltage u1 - u2 / VSM offset u1 - u2
VECTOR_G (n/M)
Can be changed: T
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: -
Min
-100.000 [V]
Description:
Offset voltage between phases L1 and L2 for the Voltage Sensing Module (VSM). The value is automatically
determined with the drive switched-off and stationary when the offset calculation is enabled. The last determined
value is saved if the offset calculation is inhibited. If the offset calculation is inhibited, then a fixed value can also be
entered here.
Dependency:
Refer to: p6903
Note:
Offset calibration is only automatically activated if the resulting motor voltage is less than 1% of the rated voltage.
p6871[0...n]
VSM offset voltage u2 - u3 / VSM offset u2 - u3
VECTOR_G (n/M)
Can be changed: T
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: -
Min
-100.000 [V]
Description:
Offset voltage between phases L2 and L3 for the Voltage Sensing Module (VSM). The value is automatically
determined with the drive switched-off and stationary when the offset calculation is enabled. The last determined
value is saved if the offset calculation is inhibited. If the offset calculation is inhibited, then a fixed value can also be
entered here.
Dependency:
Refer to: p6903
Note:
Offset calibration is only automatically activated if the resulting motor voltage is less than 1% of the rated voltage.
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Shift by -90 °
Shift by +120 °
Shift by -120 °
Shift by +150 °
Shift by -150 °
Calculated: -
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
100 [ms]
Calculated: -
Dyn. index: p0150
Unit group: -
Scaling: -
Max
100.000 [V]
Calculated: -
Dyn. index: p0150
Unit group: -
Scaling: -
Max
100.000 [V]
2 Parameters
2.2 List of parameters
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0 [ms]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0.000 [V]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0.000 [V]
745