Dependency:
Refer to: p0212
Note:
This parameter is only effective for chassis power units with 3 AC line connection and line contactors.
PDS: Power unit Data Set
p0260
Cooling unit starting time 1 / RKA start time 1
VECTOR_G
Can be changed: U, T
(Cool_unit), B_INF
Data type: FloatingPoint32
(Cool_unit)
P-Group: Converter
Not for motor type: -
Min
0.0 [s]
Description:
Sets starting time 1 to monitor the cooling unit after switch-on command.
After switching on, the following signals must be present within starting time 1:
- "RKA switched on"
- "RKA liquid flow OK"
When a fault occurs, an appropriate message is output.
Dependency:
Refer to: F49152, F49153
Note:
RKA: cooling system
p0261
Cooling unit starting time 2 / RKA start time 2
VECTOR_G
Can be changed: U, T
(Cool_unit), B_INF
Data type: FloatingPoint32
(Cool_unit)
P-Group: Converter
Not for motor type: -
Min
0.0 [s]
Description:
Sets starting time 2 to monitor the cooling unit after switch-on command.
After switching on, the following signals must be present within starting time 2:
- "RKA conductivity, no fault"
- "RKA conductivity, no alarm"
When a fault occurs, an appropriate message is output.
Dependency:
Refer to: p0266
Refer to: F49151
p0262
Cooling unit fault conductivity delay time / RKA cond t_del
VECTOR_G
Can be changed: U, T
(Cool_unit), B_INF
Data type: FloatingPoint32
(Cool_unit)
P-Group: Converter
Not for motor type: -
Min
0.0 [s]
Description:
Sets the delay time for the fault "RKA: Conductive limit value exceeded" during operation.
The fault is only output if, during operation, the conductivity exceeds the permissible fault value and the value
remains for a longer time than is set in this parameter.
Dependency:
Refer to: F49151, A49171
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
PDS6 bypass contactor feedback signal
input
PDS7 precharging/line contactor control
output
PDS7 precharging/line contactor feedback
signal input
PDS7 bypass contactor control output
PDS7 bypass contactor feedback signal
input
High
High
High
High
High
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
60.0 [s]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
1200.0 [s]
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
30.0 [s]
2 Parameters
2.2 List of parameters
Low
Low
Low
Low
Low
Access level: 3
Func. diagram: 9795
Unit selection: -
Expert list: 1
Factory setting
5.0 [s]
Access level: 3
Func. diagram: 9795
Unit selection: -
Expert list: 1
Factory setting
180.0 [s]
Access level: 3
Func. diagram: 9795
Unit selection: -
Expert list: 1
Factory setting
0.0 [s]
-
-
-
-
-