2 Parameters
2.2 List of parameters
p1325[0...n]
U/f control programmable characteristic voltage 3 / Uf char U3
VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: V/f open-loop control
Not for motor type: -
Min
0.0 [Vrms]
Description:
The programmable characteristic for the U/f control is defined using 4 points and 0 Hz/p1310.
This parameter specifies the voltage of the third point along the characteristic.
Dependency:
Refer to: p1310, p1311, p1320, p1321, p1322, p1323, p1324, p1326, p1327
p1326[0...n]
U/f control programmable characteristic frequency 4 / Uf char f4
VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: V/f open-loop control
Not for motor type: -
Min
0.00 [Hz]
Description:
The programmable characteristic for the U/f control is defined using 4 points and 0 Hz/p1310.
This parameter specifies the frequency of the fourth point along the characteristic.
Dependency:
Selects the freely programmable characteristic using p1300 = 3.
The following applies for the frequency values:
p1320 <= p1322 <= p1324 <= p1326
Otherwise, a standard characteristic is used that contains the rated motor operating point.
Refer to: p1310, p1311, p1320, p1321, p1322, p1323, p1324, p1325, p1327
Note:
Linear interpolation is carried out between the points 0 Hz/p1310, p1320/p1321 ... p1326/p1327. For output
frequencies above p1326, the characteristic is extrapolated with the gradient between the characteristic points
p1324/p1325 and p1326/p1327.
The voltage boost when accelerating (p1311) is also applied to the freely programmable U/f characteristic.
p1327[0...n]
U/f control programmable characteristic voltage 4 / Uf char U4
VECTOR_G
Can be changed: U, T
Data type: FloatingPoint32
P-Group: V/f open-loop control
Not for motor type: -
Min
0.0 [Vrms]
Description:
The programmable characteristic for the U/f control is defined using 4 points and 0 Hz/p1310.
This parameter specifies the voltage of the fourth point along the characteristic.
Dependency:
Selects the freely programmable characteristic using p1300 = 3.
Refer to: p1310, p1311, p1320, p1321, p1322, p1323, p1324, p1325, p1326
Note:
Linear interpolation is carried out between the points 0 Hz/p1310, p1320/p1321 ... p1326/p1327.
The voltage boost when accelerating (p1311) is also applied to the freely programmable U/f characteristic.
376
Calculated: CALC_MOD_ALL
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
10000.0 [Vrms]
Calculated: CALC_MOD_REG
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
10000.00 [Hz]
Calculated: CALC_MOD_REG
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
10000.0 [Vrms]
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: 6301
Unit selection: -
Expert list: 1
Factory setting
0.0 [Vrms]
Access level: 3
Func. diagram: 6301
Unit selection: -
Expert list: 1
Factory setting
0.00 [Hz]
Access level: 3
Func. diagram: 6301
Unit selection: -
Expert list: 1
Factory setting
0.0 [Vrms]
SINAMICS G130/G150