2 Parameters
2.2 List of parameters
p10006
SI TM54F acknowledgment internal event input terminal / SI ackn int event
TM54F_MA,
Can be changed: C2(95)
TM54F_SL
Data type: Integer16
P-Group: Safety Integrated
Not for motor type: -
Min
0
Description:
Select a fail-safe digital input (F-DI) for the signal "acknowledge internal event" (internal fault).
The signal is transferred to the corresponding control signal of all drives.
The falling edge at this input resets the status "internal event" in the drives.
The rising edge at this input acknowledges any existing discrepancy errors.
Value:
0:
1:
2:
3:
4:
5:
6:
7:
8:
9:
10:
255:
Dependency:
Refer to: A35081
Note:
The values "static selected" and "static deselected" result in an inactive function of the safe acknowledgment.
F-DI: Failsafe Digital Input
p10007
BI: SI TM54F forced checking procedure F-DI/F-DO signal source / SI dynF-DI/DOs_src
TM54F_MA
Can be changed: C2(95)
Data type: Unsigned32 / Binary
P-Group: Safety Integrated
Not for motor type: -
Min
-
Description:
Sets the signal source to initiate the test stop.
For example, a digital input of the Control Unit or one of the other Terminal Modules can be set as signal source.
The test stop is triggered on a 0/1 signal edge.
The TM54F must be in the "ready" state (p0010 = 0).
Dependency:
Refer to: p10001, p10003, p10041, p10046
Notice:
Digital inputs of the TM54F must not be used to trigger the test stop.
p10008
SI TM54F operating mode / SI op_mod
TM54F_MA,
Can be changed: C2(95)
TM54F_SL
Data type: Integer16
P-Group: Safety Integrated
Not for motor type: -
Min
0
Description:
Sets the operating mode for the Terminal Module 54F (TM54F).
Value:
0:
1:
Note:
Parameter being prepared. For this firmware version, the function interface is not supported.
1036
Static selected
F-DI 0 (X521.2/3/6)
F-DI 1 (X521.4/5/7)
F-DI 2 (X522.1/2/7)
F-DI 3 (X522.3/4/8)
F-DI 4 (X522.5/6/9)
F-DI 5 (X531.2/3/6)
F-DI 6 (X531.4/5/7)
F-DI 7 (X532.1/2/7)
F-DI 8 (X532.3/4/8)
F-DI 9 (X532.5/6/9)
Static deselected
Function interface
Control interface
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
255
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
1
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: 2900, 2905
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 2892
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
1