Siemens G130 List Manual page 613

Hide thumbs Also See for G130:
Table of Contents

Advertisement

p3670[0...n]
VSM 10 V input CT gain / VSM CT_gain
VECTOR_G
Can be changed: T
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: -
Min
0.000 [A]
Description:
Sets CT gain of the CT connected at the 10 V input of the Voltage Sensing Module (VSM).
The parameter specifies the current magnitude in [A] referred to the input voltage at the VSM in [V].
Example:
CT with 1 V per 200 A.
--> p3670 = 200
Dependency:
Refer to: r3671, r3672
Note:
The CT for phase 1 is connected at terminals X520.1 and X520.2 of the VSM.
The CT for phase 2 is connected at terminals X520.3 and X520.4 of the VSM.
r3671[0...n]
CO: VSM 10 V input CT 1 actual value / VSM CT 1 I_act
VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: -
Min
- [A]
Description:
Displays the current actual value from current transducer (CT) 1 at the 10 V input of the Voltage Sensing Module
(VSM).
Dependency:
Refer to: p3670
Note:
The CT for phase 1 is connected at terminals X520.1 and X520.2 of the VSM.
r3672[0...n]
CO: VSM 10 V input CT 2 actual value / VSM CT 2 I_act
VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: -
Min
- [A]
Description:
Displays the current actual value from current transducer (CT) 2 at the 10 V input of the Voltage Sensing Module
(VSM).
Dependency:
Refer to: p3670
Note:
The CT for phase 2 is connected at terminals X520.3 and X520.4 of the VSM.
r3673[0...n]
CO: VSM 10 V input 1 actual value / VSM inp 1 U_act
VECTOR_G
Can be changed: -
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: -
Min
- [V]
Description:
Displays the actual value of the voltage measured at the 10 V input 1 of the Voltage Sensing Module (VSM).
Dependency:
Refer to: p3670
Note:
10 V input 1: Terminals X520.1 and X520.2
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Calculated: -
Dyn. index: p0150
Unit group: -
Scaling: p2002
Max
1000.000 [A]
Calculated: -
Dyn. index: p0150
Unit group: -
Scaling: p2002
Max
- [A]
Calculated: -
Dyn. index: p0150
Unit group: -
Scaling: p2002
Max
- [A]
Calculated: -
Dyn. index: p0150
Unit group: -
Scaling: p2001
Max
- [V]
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 9880
Unit selection: -
Expert list: 1
Factory setting
1.000 [A]
Access level: 3
Func. diagram: 9880
Unit selection: -
Expert list: 1
Factory setting
- [A]
Access level: 3
Func. diagram: 9880
Unit selection: -
Expert list: 1
Factory setting
- [A]
Access level: 3
Func. diagram: 9880
Unit selection: -
Expert list: 1
Factory setting
- [V]