Siemens G130 List Manual page 884

Hide thumbs Also See for G130:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
[2] = Number of send net data (bytes) of all connections
[3] = Number of receive subslots of all connections
[4] = Number of receive net data (bytes) of all connections
[5] = Connection type (RT, IRT)
Dependency:
Refer to: p8929
Note:
For index 5:
Bit 0 = 1: there is at least one RT connection.
Bit 1 = 1: there is an IRT connection.
r8939
PN DAP ID / PN DAP ID
CU_G130_PN,
Can be changed: -
CU_G150_PN
Data type: Unsigned32
P-Group: -
Not for motor type: -
Min
-
Description:
Displays the DAP ID for the onboard PROFINET interface.
The combination of device ID (r8909) and DAP ID uniquely identifies a PROFINET access point.
Note:
DAP ID: Device Access Point ID
List of the SINAMICS DAP IDs:
20008 hex: CBE20 V4.6
20009 hex: CBE20 V4.7
2000A hex: CBE20 V4.8
20108 hex: CU310-2 PN V4.6
20109 hex: CU310-2 PN V4.7
2010A hex: CU310-2 PN V4.8
20308 hex: CU320-2 PN V4.6
20309 hex: CU320-2 PN V4.7
2030A hex: CU320-2 PN V4.8
p8940[0...239]
CBE2x Name of Station / CBE2x Name Stat
CU_G130_PN (PN
Can be changed: U, T
CBE20),
Data type: Unsigned8
CU_G150_PN (PN
P-Group: -
CBE20),
Not for motor type: -
CU_G130_DP (PN
CBE20),
Min
CU_G150_DP (PN
-
CBE20)
Description:
Sets the station name for the Communication Board Ethernet 20/25 (CBE20/CBE25).
Dependency:
Refer to: p8945, r8950
Note:
An ASCII table (excerpt) can be found, for example, in the appendix to the List Manual.
The interface configuration (p8940 and following) is activated with p8945.
The parameter is not influenced by setting the factory setting.
p8941[0...3]
CBE2x IP address / CBE2x IP addr
CU_G130_PN (PN
Can be changed: U, T
CBE20),
Data type: Unsigned8
CU_G150_PN (PN
P-Group: -
CBE20),
Not for motor type: -
CU_G130_DP (PN
CBE20),
Min
CU_G150_DP (PN
0
CBE20)
Description:
Sets the IP address for the Communication Board Ethernet 20/25 (CBE20/CBE25).
Dependency:
Refer to: p8945, r8951
884
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
255
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
SINAMICS G130/G150

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

SinamicsG150

Table of Contents